157
Reference Manual
00809-0100-4021, Rev GC
Section 4: F
OUNDATION
fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
L_TYPE is Indirect
When an inferred measurement is made based on the sensor measurement, set the XD_SCALE
to represent the operating range that the sensor will see in the process. Determine the inferred
measurement values that correspond to the XD_SCALE 0 and 100% points and set these for the
OUT_SCALE.
Note
To avoid configuration errors, only select Engineering Units for XD_SCALE and OUT_SCALE that
are supported by the device. The supported units are:
When the engineering units of the XD_SCALE are selected, this changes the engineering units of
the PRIMARY_VALUE_RANGE in the Transducer Block to the same units.
THIS IS THE ONLY WAY TO CHANGE THE ENGINEERING UNITS IN THE SENSOR TRANSDUCER
BLOCK, PRIMARY_VALUE_RANGE PARAMETER.
Configuration examples
Sensor Type: 4-wire, Pt 100
= 385.
Desired measurement process temperature in the –200 to 500 °F range. Monitor the
transmitter electronics temperature in the –40 to 185 °F range.
Transducer block
If host system supports methods:
1.
Click on Methods.
2.
Choose Sensor Connections.
(1)
3.
Follow on-screen instruction to setup Sensor 1 as a 4-wire, Pt 100
= 385.
If host system does not support methods:
1.
Put transducer block into OOS mode.
a.
Go to MODE_BLK.TARGET.
b. Choose OOS (0x80).
Temperature (channel 1 and 2)
Terminal (body) temperature
°
C
°
C
°
F
°
F
K
K
°R
R
mV
(1)
Some choices may not be available due to the current configuration of the device.
Examples:
a) Sensor 2 cannot be configured at all if Sensor 1 is set up as a 4-wire sensor
b) If Sensor 2 is configured, Sensor 1 can not be set up as a 4-wire sensor (and vise-versa)
c) When selecting a thermocouple as the sensor type, a 3- or 4-wire connection cannot be selected.
In this situation, configure the other sensor as “Not used.” This will clear the dependencies that are preventing the configuration of the desired
sensor.
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......