219
Reference Manual
00809-0100-4021, Rev GC
Appendix B: Product Certifications
April 2014
N1
ATEX Type n
Certificate: BAS01ATEX3432X [HART]; Baseefa03ATEX0709X [Fieldbus]
Standards Used: EN 60079-0: 2012, EN 60079-15: 2010
Markings: HART:
II 3G Ex nA IIC T5/T6 Gc; T6(–40 °C
T
a
50 °C), T5(–40 °C
T
a
75
°C); Fieldbus:
II 3G Ex nA IIC T5 Gc; T5(–40 °C
T
a
75 °C);
Special Condition for Safe Use (X):
1.
When fitted with the transient terminal options, the equipment is not capable of
withstanding the 500 V electrical strength test as defined in clause 6.5.1 of EN
60079-15: 2010. This must be taken into account during installation.
ND
ATEX Dust
Certificate Number: FM12ATEX0065X
Standards Used: EN 60079-0: 2012, EN 60079-31: 2009, EN 60529:1991 +A1:2000
Markings:
II 2D Ex tb IIIC T130 °C Db, (–40 °C
T
a
70 °C); IP66
at the end of the Product Certifications section for process temperatures.
Special Conditions for Safe Use (X):
1.
See certificate for ambient temperature range.
2.
The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3.
Guard the LCD display cover against impact energies greater than 4 joules.
4.
Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
International
E7
IECEx
Flameproof
Certificate: IECEx FMG 12.0022X
Standards Used: IEC 60079-0:2011, IEC 60079-1: 2007-04, IEC 60079-31: 2008
Markings: Ex d IIC T6…T1 Gb, T6(–50 °C
T
a
40 °C), T5…T1(–50 °C
T
a
60 °C);
Ex tb IIIC T130 °C Db, (–40 °C
T
a
70 °C); IP66;
at the end of the Product Certifications section for process temperatures.
Special Conditions for Safe Use (X):
1.
See certificate for ambient temperature range.
2.
The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3.
Guard the LCD display cover against impact energies greater than 4 joules.
4.
Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......