25
Reference Manual
00809-0100-4021, Rev GC
Section 2: Installation
April 2014
Figure 2-14. Load Limits
F
OUNDATION
fieldbus
Powered over F
OUNDATION
fieldbus with standard fieldbus power supplies, the transmitter
operates between 9.0 and 32.0 Vdc, 11 mA maximum. Transmitter power terminals are rated to
42.4 Vdc.
The power terminals on the 3144P with F
OUNDATION
fieldbus are polarity insensitive.
2.6.1
Surges/transients
The transmitter will withstand electrical transients of the energy level usually encountered in
static discharges or induced switching; however, high-voltage transients, such as those induced
in wiring from nearby lightning strikes, can damage both the transmitter and the sensor.
The integral transient protection terminal block (option code T1) protects against high-voltage
transients. The integral transient protection terminal block is available as an ordered option, or
as an accessory. Refer to
“Transient protection (option code T1)” on page 198
for more
information.
2.6.2
Grounding
Sensor shielding
The currents in the leads induced by electromagnetic interference can be reduced by shielding.
Shielding carries the current to ground and away from the leads and electronics. If the ends of
the shields are adequately grounded, only a small amount of current will actually enter the
transmitter.
If the ends of the shield are left ungrounded, voltage is created between the shield and the
transmitter housing and also between the shield and earth at the element end. The transmitter
may not be able to compensate for this voltage, causing it to lose communication and/or go into
alarm. Instead of the shield carrying the currents away from the transmitter, the currents will
now flow through the sensor leads into the transmitter circuitry where it will interfere with the
circuit operation.
Maximum Load = 40.8 X (Supply Voltage - 12.0)
1240
1000
750
250
0
10
12.0
20
30
40 42.4
Supply Voltage (Vdc)
Operating
Region
4–20 mA dc
Lo
ad
(
O
h
m
s)
500
1100
Содержание Rosemount
Страница 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Страница 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Страница 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Страница 233: ...227 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 234: ...228 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 235: ...229 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 237: ...231 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 238: ...232 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 244: ...238 Reference Manual 00809 0100 4021 Rev GC Appendix B Product Certifications April 2014 Product Certifications ...
Страница 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Страница 251: ......