Instruction Manual
Section 9: Alarm Relay Functions
LIQ-MAN-56
April 2017
Alarm Relay Functions
69
A schematic of the Delay Timer operation is shown:
9.3.2
Setup
Access Delay Timer by pressing ENTER/MENU from the main screen and then Program/Relays/
Configure Relay. From the main relay programming screen, program this feature as follows:
1.
Relay:
Assign a relay by highlighting the desired relay 1-4 and press ENTER/MENU.
2.
Type:
Select Delay Timer as the relay type and press ENTER/MENU.
3.
Assign:
Assign S1 (sensor 1), S2 (sensor 2 if available) or other available parameters to
the designated relay and press ENTER/MENU.
4.
Logic:
Set High for high reading setpoint logic or Low relay logic for low reading setpoint
logic and press ENTER/MENU.
5.
Setpoint:
Enter the desired setpoints value. This will activate an alarm event when the
process measurement reaches the entered setpoint value. Press ENTER/MENU. See
Table 9-2 for entry limits.
6.
Deadband:
To set deadband as a measurement value, enter the change in the process
value needed after the relay deactivates to return to normal (and thereby preventing re-
peated alarm activation). Press ENTER/MENU.
7. Select
NEXT
Press ENTER/MENU to advance to the next setup screen.
8.
On time:
Enter the time in minutes (X.X min) for the relay to remain energized. The as-
signed measurement value will be on hold during this time.
9.
Delay time:
Enter the time in minutes (X.X min) to take the assigned measurement off
hold after the relay is re-energized to begin reporting live values.
10.
Normal state:
Set the normal alarm condition as Open or Closed and press
ENTER/MENU. Program the normal state to define the desired alarm default state to nor-
mally open or normally closed upon power up.
Figure 9-2. Delay Timer Alarm operation
high alarm
t
n
i
o
p
t
e
s
deadband
time
PV
delay time
on time
measurement
Содержание Rosemount 56
Страница 1: ...Instruction Manual LIQ MAN 56 Rev D April 2017 Rosemount 56 Advanced Dual Input Analyzer ...
Страница 2: ......
Страница 10: ...iv Table of Contents Instruction Manual April 2017 LIQ MAN 56 ...
Страница 30: ...Section 2 Installation Instruction Manual April 2017 LIQ MAN 56 20 Installation ...
Страница 40: ...30 Wiring Section 3 Wiring Instruction Manual April 2017 LIQ MAN 56 ...
Страница 64: ...Section 6 Programming Measurements Instruction Manual April 2017 LIQ MAN 56 54 ...
Страница 76: ...Section 8 Time Proportional Control Instruction Manual April 2017 LIQ MAN 56 66 ...
Страница 124: ...Section 13 Maintenance Instruction Manual April 2017 LIQ MAN 56 114 ...
Страница 126: ...Section 14 Return of Material Instruction Manual April 2017 LIQ MAN 56 116 ...