Direct load switching cassette
Figure 4-1: Direct Load Switching (2-wire) Cassette (Red Label) – Code T
1
2
3
L
N
0V
I
L
DPST
+V
Fuse 2A(T)
R
R = External load (must be fitted)
N = Neutral
L = Live
Note
A DPST (Double Pole, Single Throw) on/off switch must be fitted for safe disconnection of
the power supply. Fit the DPST switch as near as possible to the level switch. Keep the
DPST switch free of obstructions. Label the DPST switch to indicate it is the supply
disconnection device for the level switch.
Note
The Rosemount 2120 requires a minimum current to operate (I
OFF
), which continues to
flow when the output is ‘off’. If selecting a relay to wire in series with the Rosemount 2120,
ensure the drop-out voltage of the relay is greater than the voltage generated across the
relay coil when I
OFF
flows through it.
Table 4-1: Electrical Parameters
Parameter
Value
U
20 - 60 Vdc or 20 - 264 Vac (50/60 Hz)
I
OFF
< 4 mA
I
L
20 - 500 mA
I
PK
5 A, 40 ms (inrush)
Electrical installation
Reference Manual
March 2022
00809-0100-4030
36
Reference Manual
Содержание Rosemount 2120
Страница 1: ...Reference Manual 00809 0100 4030 Rev GA March 2022 Rosemount 2120 Level Switch Vibrating Fork ...
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual March 2022 00809 0100 4030 8 Reference Manual ...
Страница 14: ...Level switch overview Reference Manual March 2022 00809 0100 4030 14 Reference Manual ...
Страница 32: ...Mechanical installation Reference Manual March 2022 00809 0100 4030 32 Reference Manual ...
Страница 81: ...Reference Manual 00809 0100 4030 March 2022 Rosemount 2120 Level Switch 81 ...