Relay DPCO cassette (12 Vdc nominal version)
Figure 4-4: Relay DPCO Cassette, 12 Vdc Nominal Version (Green Label) – Code E
Example of external wiring
Isolate supply before making connections.
U = 9 - 30 V (dc)
I < 4 mA
4
cos
f
= 1;
L/R = 0 ms
I
MAX
= 2 A
cos
f
= 0.4;
L/R = 7 ms
I
MAX
= 1 A
U
MAX
= 30 V
U
MAX
= 30 V
P
MAX
= 60 W
P
MAX
= 30 W
4
5
6
NC
C
NO
7
8
9
NC
C
NO
NC C NO
NC C NO
0V
Fuse 0.5 (T)
DPST
+V
Note
A DPST (Double Pole, Single Throw) on/off switch must be fitted for safe disconnection of
the power supply. Fit the DPST switch as near as possible to the Rosemount 2120. Keep
the DPST switch free of obstructions. Label the DPST switch to indicate it is the supply
disconnection device for the Rosemount 2120.
Table 4-8: Electrical Parameters
Parameter
Value
U
9 - 30 Vdc
I
< 4 mA
Table 4-9: NC, C, and NO Terminals
Parameter
Resistive load
Inductive load
cos
ϕ
1
0.4
L/R
0 ms
7 ms
I
MAX
2 A
1 A
U
MAX
30 V
30 V
P
MAX
60 W
30 W
Electrical installation
Reference Manual
March 2022
00809-0100-4030
42
Reference Manual
Содержание Rosemount 2120
Страница 1: ...Reference Manual 00809 0100 4030 Rev GA March 2022 Rosemount 2120 Level Switch Vibrating Fork ...
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual March 2022 00809 0100 4030 8 Reference Manual ...
Страница 14: ...Level switch overview Reference Manual March 2022 00809 0100 4030 14 Reference Manual ...
Страница 32: ...Mechanical installation Reference Manual March 2022 00809 0100 4030 32 Reference Manual ...
Страница 81: ...Reference Manual 00809 0100 4030 March 2022 Rosemount 2120 Level Switch 81 ...