Other recommendations
•
Always install in the normally “on” state.
—
High-level alarm: recommended Mode setting is
Dry = on
.
—
Low-level alarm: recommended Mode setting is
Wet = on
.
•
Avoid:
—
Installing near to liquid entering the tank at the filling-point.
—
Heavy splashing on the forks.
Increasing the sensor output delay reduces accidental detection caused by splashing.
•
Always ensure:
—
The overall system is tested during commissioning by using the local magnetic test
point.
—
The installation does not create tank crevices around the forks where a liquid
medium may collect. This event can happen with high-viscosity and high-density
liquids.
—
The forks do not come into contact with the vessel (tank) or pipe wall, internal
fittings, or any other obstructions.
•
Extra consideration is needed if the plant vibration is close to the 1400 Hz operating
frequency of the fork.
Required supports for extended fork
Supporting the extended fork avoids long fork length vibration.
Figure 3-8: Vertical Installation (Standard)
A
B
B
A. Maximum 3.28 ft. (1.0 m)
B. 3.28 ft. (1.0 m)
Reference Manual
Mechanical installation
00809-0100-4030
March 2022
Rosemount 2120 Level Switch
23
Содержание Rosemount 2120
Страница 1: ...Reference Manual 00809 0100 4030 Rev GA March 2022 Rosemount 2120 Level Switch Vibrating Fork ...
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual March 2022 00809 0100 4030 8 Reference Manual ...
Страница 14: ...Level switch overview Reference Manual March 2022 00809 0100 4030 14 Reference Manual ...
Страница 32: ...Mechanical installation Reference Manual March 2022 00809 0100 4030 32 Reference Manual ...
Страница 81: ...Reference Manual 00809 0100 4030 March 2022 Rosemount 2120 Level Switch 81 ...