Relay DPCO cassette (standard version)
Figure 4-3: Relay DPCO Cassette, Standard Version (Green Label) – Code V
L
N
0V
Fuse 0.5 (T)
DPST
+V
1
2
3
4
5
6
7
8
9
NC C NO
NC C NO
Note
A DPST (Double Pole, Single Throw) on/off switch must be fitted for safe disconnection of
the power supply. Fit the DPST switch as near as possible to the level switch. Keep the
DPST switch free of obstructions. Label the DPST switch to indicate it is the supply
disconnection device for the level switch.
Table 4-5: Electrical Parameters
Parameter
Value
U
20 - 60 Vdc or 20 - 264 Vac (50/60Hz)
I
< 6 mA
Table 4-6: NC, C, and NO Terminals
Parameter
Resistive load
Inductive load
cos
ϕ
1
0.4
L/R
0 ms
7 ms
I
MAX
5 A
3.5 A
U
MAX
ac
250 V
250 V
dc
30 V
30 V
P
MAX
ac
1250 VA
875 VA
dc
240 W
170 W
Electrical installation
Reference Manual
March 2022
00809-0100-4030
40