Always ensure:
•
There is sufficient distance between build-up on the tank wall and the fork.
•
There is no risk of ‘bridging’ the level switch forks.
Examples of products that can create ‘bridging’ of forks and impair performance are
dense paper slurries and bitumen.
Figure 3-2: Avoid Product Build-up
OK
Operating temperature and pressure ranges
Ensure the process is operating within the instrument operating temperature and pressure
ranges.
Liquid density requirements
Minimum liquid density is 37.5 lb/ft
3
(600 kg/m
3
).
Liquid viscosity range
Up to 10000 cP (centiPoise)
Solids content in the liquid medium
As a guideline, the maximum solid particle diameter in the liquid process medium is 0.2 in.
(5 mm). Extra consideration is needed when solid particles are bigger than 0.2 in. (5 mm)
and advice should be sought from Emerson.
Foams
In almost all cases, the Rosemount 2120 is insensitive to foams (i.e. does not see the
foam).
However in rare occasions, some very dense foams may be seen as liquid; known examples
of this are found in ice-cream and orange juice manufacturing.
Mechanical installation
Reference Manual
March 2022
00809-0100-4030
18
Reference Manual
Содержание Rosemount 2120
Страница 1: ...Reference Manual 00809 0100 4030 Rev GA March 2022 Rosemount 2120 Level Switch Vibrating Fork ...
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual March 2022 00809 0100 4030 8 Reference Manual ...
Страница 14: ...Level switch overview Reference Manual March 2022 00809 0100 4030 14 Reference Manual ...
Страница 32: ...Mechanical installation Reference Manual March 2022 00809 0100 4030 32 Reference Manual ...
Страница 81: ...Reference Manual 00809 0100 4030 March 2022 Rosemount 2120 Level Switch 81 ...