4.2.2
Cable glands/conduits
For intrinsically safe, explosion-proof/flameproof, and dust-proof installations, only use
certified cable glands or conduit entry devices. Ordinary location installations can use
suitably rated cable glands or conduit entry devices to maintain the Ingress Protection (IP)
rating.
Unused conduit entries must always be sealed with a suitably rated blanking/stopping
plug.
Note
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical
equipment.
4.2.3
Power supply
The power supply requirements are dependent on the electronics selected.
•
Direct load switching: 20 - 60 Vdc or 20 - 264 Vac (50/60 Hz)
•
PNP/PLC electronics: 20 - 60 Vdc
•
Relay DPCO (Double Pole Changeover) electronics (standard): 20 - 60 Vdc or
20 - 264 Vac (50/60 Hz)
•
Relay DPCO electronics (12 Vdc nominal): 9 - 30 Vdc
•
NAMUR electronics: 8 Vdc
•
8/16 mA electronics: 24 Vdc
4.2.4
Hazardous areas
When the device is installed in hazardous areas (classified locations), local regulations and
the conditions-of-use specified in applicable certificates must be observed. Review the
Rosemount 2120
4.2.5
Wiring diagrams
CAUTION
•
Before use, check the cable glands and blanking plugs are suitably rated.
•
Isolate supply before connecting the switch or removing the electronics.
•
The Protective Earth (PE) terminal must be connected to an external earthing
system.
Note
When replacing a cassette, it is important to re-calibrate.
Reference Manual
Electrical installation
00809-0100-4030
March 2022
Rosemount 2120 Level Switch
35
Содержание Rosemount 2120
Страница 1: ...Reference Manual 00809 0100 4030 Rev GA March 2022 Rosemount 2120 Level Switch Vibrating Fork ...
Страница 4: ...4 ...
Страница 8: ...Introduction Reference Manual March 2022 00809 0100 4030 8 Reference Manual ...
Страница 14: ...Level switch overview Reference Manual March 2022 00809 0100 4030 14 Reference Manual ...
Страница 32: ...Mechanical installation Reference Manual March 2022 00809 0100 4030 32 Reference Manual ...
Страница 81: ...Reference Manual 00809 0100 4030 March 2022 Rosemount 2120 Level Switch 81 ...