ROC364 Instruction Manual
B-15
Local Display Panel
Rev Jun/05
>VIEW
Plate Change
UP DOWN ENTER
MENU
Figure B-22. AGA Menu Display
B.3.7.1 AGA Point Display 1 – View
Figure B-23 shows a typical View AGA Point Display 1. Table B-14 describes the parameters shown on
an AGA Point Display 1.
AGA2 MCF/DAY
CUR RATE
5003.34
ALM 00000000
SCAN PREV NEXT MENU
Figure B-23. AGA Point Display 1
Table B-14. AGA Point Display 1 Parameters
Parameter Description
Meter ID Tag
10-character identifier for the AGA point.
Units
Unit of measurement identifier for the engineering units (EU) assigned to the AGA point.
CUR RATE
Current instantaneous flow rate in volume units/day.
ALM
8-bit field. If a bit is set to “1”, the alarm is active. If a bit is set to “0,” the alarm is cleared.
Figure B-24 shows the alarm code bits and the alarms they represent for an AGA point.
Alarm
Code
0 0
0 0
0 0
0 0
Manual Mode
Low Alarm
No Flow
Not Used
Not Used
High Alarm
Not Used
Not Used
Figure B-24. AGA Point Display 1 Alarm Code Bits