(06.028) is the same as the sign of
Output Power
(05.003).
Parameter
06.028
Running Cost
Short description
Displays the running cost of the drive
Mode
Open
‑
Loop
Minimum
-32000
Maximum
32000
Default
Units
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
See
Energy Cost Per kWh
(06.027).
Parameter
06.029
Hardware Enable
Short description
Set to 1 to enable the hardware of the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
2ms read
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Hardware Enable
(06.029) normally shows the hardware enable state based on the state of the safe torque off system. However, drive I/O can be routed
to
Hardware Enable
(06.029) to reduce the disable time. See description of the enable logic for more details.
Parameter
06.030
Run Forward
Short description
Set to to give the drive a run forward signal
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
2ms read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
If
Reference Selected Indicator
(01.049) is not equal to 4 then
Run Forward
(06.030) can be used to make the Final drive run active and
Reverse Select
(01.012) = 0, i.e. to make the drive run in the forward direction. See description of sequencer logic for more details.
Parameter
06.032
Run Reverse
Short description
Set to 1 to give the drive a run reverse signal
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
2ms read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
If
Reference Selected Indicator
(01.049) is not equal to 4 then
Run Reverse
(06.032) can be used to make the Final drive run active and
Reverse Select
(01.012) = 1, i.e. to make the drive run in the reverse direction. See description of sequencer logic for more details.
Parameter
06.033
Forward/Reverse
Short description
Set to 1 to reverse the direction of the motor
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
2ms read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
If
Reference Selected Indicator
(01.049) is not equal to 4 then
Forward/Reverse
(06.033) can be used to force the state of Reverse Select (01.012). If
Forward/Reverse
(06.033) = 1 then
Reverse Select
(01.012) = 1. If
Forward/Reverse
(06.033) = 0 then
Forward/Reverse
(06.033) = 0 unless it is set to 1
by the rest of the normal run or jog logic. See description of sequencer logic for more details.
Parameter
06.034
Run
Short description
Set to 1 to give the drive a run signal
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
2ms read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
91
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...