Internal I/O Identifier
(11.068)
Analogue Input
1
Analogue Input 2 Analogue Input 3
0: Standard
Analogue and
Digital I/O
Bipolar Voltage,
Current
Bipolar Voltage,
Current
Bipolar Voltage,
Thermistor,
Disabled
1: Digital I/O
Not present
Not present
Thermistor,
Disabled
2: HVAC Analogue
and Digital I/O
UnipolarVoltage,
Current,
Thermistor
Unipolar
Voltage, Current,
Thermistor
Not present
Parameter
07.001
Analog Input 1
Short description
Displays the value of analog input 1
Mode
Open
‑
Loop
Minimum
-100.00
Maximum
100.00
Default
Units
%
Type
16 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
2
Coding
RO, FI, ND, NC, PT
Each analogue input has a resolution of 11 bits plus sign. The inputs can operate in different modes (defined by
Analog Input 1 Mode
(07.007) for
analogue input 1). These modes include voltage, current and thermistor modes. The available modes depend on the hardware configuration and are
given in the table below.
The "Input Level" is defined for the different modes in the table below.
Mode
Input Level
Voltage
(Input Voltage / 10V) x 100.00%
0-20mA
(Input Current / 20mA) x 100.00%
20-0mA
((20mA - Input Current) / 20mA) x 100.00%
4-20mA
((Input Current - 4mA) / 16mA) x 100.00%
20-4mA
((20mA - Input Current) / 16mA) x 100.00%
Thermistor
(Input resistance / 10K Ohm) x 100%
Analog Input 1
(07.001) is derived as follows:
Limits
A
1
is the value after the minimum and maximum limits are applied.
If
Analog Input 1 Minimum
(07.040) ≥
Analog Input 1 Maximum
(07.043) then:
A
1
= 0.00% whatever the input level.
If
Analog Input 1 Minimum
(07.040) < 0.00% and
Analog Input 1 Maximum
(07.043) > 0.00% then:
A
1
= Input Level x (100.00% /
Analog Input 1 Maximum
(07.043))
A
1
is then limited between -100% and +100%.
Otherwise:
Input Level is limited between
Analog Input 1 Minimum
(07.040) and
Analog Input 1 Maximum
(07.043)
A
1
= [Input Level -
Analog Input 1 Minimum
(07.040)] x 100.00% / (
Analog Input 1 Maximum
(07.043) -
Analog Input 1 Minimum
(07.040))
For thermistor modes it should be noted that
Analog Input 1 Minimum
(07.040) and
Analog Input 1 Minimum
(07.040) have no effect and that the input
resistance is limited between 0 and 5K Ohms.
Parameter
07.002
Analog Input 2
Short description
Displays the value of analog input 2
Mode
Open
‑
Loop
Minimum
-100.00
Maximum
100.00
Default
Units
%
Type
16 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
2
Coding
RO, FI, ND, NC, PT
See
Analog Input 1
(07.001).
Parameter
07.004
Monitored Temperature 1
Short description
Displays the temperature set up by Temperature Monitor Select 1
Mode
Open
‑
Loop
Minimum
-250
Maximum
250
Default
Units
°C
Type
16 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
113
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...