Value
Text
0
Volts
1
0-20mA
2
20-0mA
3
4-20mA
4
20-4mA
See
Analog Output 2 Source
(07.022).
Parameter
07.025
Calibrate Analog Input 1 Full Scale
Short description
Caibrates the input level for analog input 1
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, NC
For analog input 1, and in voltage mode only, the full scale value used to determine the input level can be changed from 10V by calibrating the input.
The calibration process is triggered by setting
Calibrate Analog Input 1 Full Scale
(07.025) to one.
Calibrate Analog Input 1 Full Scale
(07.025) is
cleared automatically when the calibration process is complete. After calibration the actions are as follows:
Input voltage
during
calibration
Result
V < 1.5V
The calibration result is ignored and the full scale is set
to 10V.
Analog Input 1 Full Scale
(07.051) is set to zero.
1.5V < V < 2.5V The calibration result is ignored and the full scale or
Analog Input 1 Full Scale
(07.051) are not affected.
V > 2.5V
The calibration result is used to set full scale and the
value is also stored in
Analog Input 1 Full Scale
(07.051).
It should be noted that
Analog Input 1 Full Scale
(07.051) is a power-down save parameter, and so the result is automatically retained after power-
down.
Parameter
07.026
Analogue Input 1 Fast Update Active
Short description
Analogue Input 1 Fast Update Active
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Analogue Input 1 Fast Update Active
(07.026) is one if the destination for analogue input 1 is being updated at the fast rate of 250us.
Parameter
07.027
Analogue Input 2 Fast Update Active
Short description
Analogue Input 2 Fast Update Active
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Analogue Input 2 Fast Update Active
(07.027) is one if the destination for analogue input 1 is being updated at the fast rate of 250us.
Parameter
07.028
Analog Input 1 Current Loop Loss
Short description
Displays when analog input 1 falls below 3mA
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
If
Analog Input 1 Mode
(07.007) is set to any of the 4-20mA or 20-4mA modes and the current falls below 3mA then
Analog Input 1 Current Loop Loss
(07.028) is set to one. If the current is more than 3mA or any other mode is selected then
Analog Input 1 Current Loop Loss
(07.028) is set to zero.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
119
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...