See
Monitored Temperature 1
(07.004) for details.
Parameter
07.007
Analog Input 1 Mode
Short description
Defines the mode of analog input 1
Mode
Open
‑
Loop
Minimum
-4
Maximum
9
Default
4
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
Description
‑
4
4-20mA Low
4-20mA low value on current loss
‑
3
20-4mA Low
20-4mA low value on current loss
‑
2
4-20mA Hold
4-20mA hold at level before loss on current loss
‑
1
20-4mA Hold
20-4mA hold at level before loss on current loss
0
0-20mA
0-20mA
1
20-0mA
20-0mA
2
4-20mA Trip
4-20mA trip on current loss
3
20-4mA Trip
20-4mA trip on current loss
4
4-20mA
4-20mA no action on loss
5
20-4mA
20-4mA no action on loss
6
Volt
Voltage
7
Therm Short Cct
Temperature measurement input with short circuit detection
8
Thermistor
Temperature measurement without short circuit detection
9
Therm No Trip
Temperature measurement input with no trips
The table below gives all the possible input modes for analog inputs 1 and 2.
Mode
Function
4-20mA Low
4-20mA low value on current loss (1)
20-4mA Low
20-4mA low value on current loss (1)
4-20mA Hold
4-20mA hold at level before loss on current loss (2)
20-4mA Hold
20-4mA hold at level before loss on current loss (2)
0-20mA
0-20mA
20-0mA
20-0mA
4-20mA Trip
4-20mA trip on current loss (1), (3)
20-4mA Trip
20-4mA trip on current loss (1), (3)
4-20mA
4-20mA no action on loss (1)
20-4mA
20-4mA no action on loss (1)
Voltage
Voltage
Therm Short
Cct
Temperature measurement input with short circuit
detection
Thermistor
Temperature measurement without short circuit detection
Therm No Trip Temperature measurement input with no trips
Disabled
Input always zero (4)
(1) Analogue input level is 0.00% if the current is below 3mA.
(2) Analogue input level remains at the value it had in the previous sample before the current fell below 3mA.
(3) A
An Input 1 Loss
is initiated if the current falls below 3mA.
(4) When the Digital I/O only is present this mode is used disable the current source as the input is on a shared connection with Digital Output 2.
Parameter
07.008
Analog Input 1 Scaling
Short description
Defines the scaling factor of analog input 1
Mode
Open
‑
Loop
Minimum
0.000
Maximum
10.000
Default
1.000
Units
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
3
Coding
RW
Analog Input 1
(07.001) is modified by
Analog Input 1 Scaling
(07.008),
Analog Input 1 Offset
(07.030) and
Analog Input 1 Invert
(07.009) before it is
routed to its destination as follows:
A
1O
=
Analog Input 1
(07.001) +
Analog Input 1 Offset
(07.030)
A
1O
is the value after the offset has been applied and is limited between -100.00% and 100.00%
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
115
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...