VM_SPEED_FREQ_REF_UNIPOLAR[MIN] = 0.0
Identifier
VM_SPEED_FREQ_USER_REFS
Description
Range applied to analogue reference parameters
Units
Open-loop: Hz
RFC-A, RFC-S: rpm or mm/s
Range of [MIN]
Open-loop: -550.00 to 550.00
RFC-A, RFC-S: -50000.0 to 50000.0
Range of [MAX]
Open-loop: 0.0 to 550.00
RFC-A, RFC-S: 0.0 to 50000.0
This variable maximum is applied to
Analogue Reference 1
(01.036) and
Analogue Reference 2
(01.037). It should be noted that in Open-loop mode the
analogue reference parameters have two decimal places.
The maximum applied to these parameters is the same as other frequency reference parameters.
VM_SPEED_FREQ_USER_REFS [MAX] = VM_SPEED_FREQ_REF[MAX]
However the minimum is dependent on
Negative Reference Clamp Enable
(01.008) and
Bipolar Reference Enable
(01.010).
Negative Reference
Clamp Enable
(01.008)
Bipolar
Reference
Enable
(01.010)
VM_SPEED_FREQ_USER_REFS[MIN]
0
0
If
Select Motor 2 Parameters
(11.045) = 0
Minimum Reference
Clamp
(01.007), otherwise
M2 Minimum Reference Clamp
(21.002)
0
1
-VM_SPEED_FREQ_REF[MAX]
1
0
0.0
1
1
-VM_SPEED_FREQ_REF[MAX]
Identifier
VM_STD_UNDER_VOLTS
Description
Range applied to the standard under voltage threshold
Units
V
Range of [MIN]
0 to 1150
Range of [MAX]
0 to 1150
VM_STD_UNDER_VOLTS[MAX] = VM_DC_VOLTAGE_SET / 1.1
VM_STD_UNDER_VOLTS[MIN] is voltage rating dependent. See the table below.
Voltage level
200V
400V
575V
690V
VM_STD_UNDER_VOLTS[MIN]
175
330
435
435
Identifier
VM_SUPPLY_LOSS_LEVEL
Description
Range applied to the supply loss threshold
Units
V
Range of [MIN]
0 to 1150
Range of [MAX]
0 to 1150
VM_SUPPLY_LOSS_LEVEL[MAX] = VM_DC_VOLTAGE_SET[MAX]
VM_SUPPLY_LOSS_LEVEL[MIN] is drive voltage rating dependent. See the table below.
Voltage level
200V 400V
575V
690V
VM_SUPPLY_LOSS_LEVEL[MIN]
205
410
540
540
Identifier
VM_SWITCHING_FREQUENCY
Description
Range applied to the maximum switching frequency parameters
Units
User units
Range of [MIN]
0
Range of [MAX]
0 to 6
VM_SWITCHING_FREQUENCY[MAX] = Power stage dependent
VM_SWITCHING_FREQUENCY[MIN] = 0 for motor control modes, or 1 for Regen mode (subject to the maximum)
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
17
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...