Parameter
01.050
Preset Selected Indicator
Short description
Displays which preset is currently selected
Mode
Open
‑
Loop
Minimum
1
Maximum
8
Default
Units
Type
8 Bit Volatile
Update Rate
4ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
See
Reference Selector
(01.014).
Parameter
01.051
Power-up Keypad Control Mode Reference
Short description
Defines which value of keypad control mode reference is displayed at power-up
Mode
Open
‑
Loop
Minimum
0
Maximum
2
Default
0
Units
Type
8 Bit User Save
Update Rate
Power-up read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Reset
1
Last
2
Preset
Power-up Keypad Control Mode Reference
(01.051) defines the value written to
Keypad Control Mode Reference
(01.017) at power-up as given below.
Power-
up Keypad Control Mode Reference
(01.051)
Value written to
Keypad Control Mode Reference
(01.017) at
power-up
0
0.0
1
The value in
Keypad Control Mode Reference
(01.017) at the
previous power-down
2
The value saved in
Preset Reference 1
(01.021)
Parameter
01.052
Hand/Off/Auto Operating Mode
Short description
Defines the hand/off/auto operating mode of the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
3
Default
1
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
Hand/Off/Auto Operating Mode
(01.052) defines the operating mode for this system as given in below.
Hand/Off/Auto Operating Mode
(01.052)
Operating mode
0
Hand/Off/Auto system disabled
1
Hand/Off/Auto system enabled
Auto state at power-up
2
Hand/Off/Auto system enabled
Off state at power-up
3
Hand/Off/Auto system enabled
Off state at power-up if off or hand state at previous power-down
Auto state if auto state at previous power-down
Hand/Off/Auto mode is an additional state machine that directly controls
Reference Selected Indicator
(01.049) and
Keypad Control Mode Reference
(01.017). When Hand/Off/Auto mode is active the drive state and keypad keys are defined as shown in the tables below.
Hand/Off/Auto state
Equivalent normal state
Off Ready with
Reference Selected Indicator
(01.049) = 4
Hand
Run with
Reference Selected Indicator
(01.049) =
4
Auto
Reference Selected Indicator
(01.049) defined by
the reference selector system
32
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...