PID1 Mode Selector
(14.059) can be used to select the feedback and error as shown in the table below. It should be noted that PID controller 2 will
operate normally even when its feedback or error has been selected for PID controller 1. However, if
PID1 Mode Selector
(14.059) is non-zero PID
controller 2 enable is controlled directly by the enable state of PID controller 1.
PID1 Mode Selector
(14.059)
Feedback
Error
0: Fbk1
FBK1
ERR1
1: Fbk2
FBK2
ERR1
2: Fbk1 + Fbk2
FBK1 + FBK2
ERR1
3: Min Fbk
Lowest of FBK1 or FBK2
ERR1
4: Max Fbk
Highest of FBK1 or FBK2
ERR1
5: Av Fbk
(FBK1 + FBK2) / 2
ERR1
6: Min Error
FBK1
If |ERR1| ≤ |ERR2| then ERR1
Else ERR2
7: Max Error
FBK1
If |ERR1| ≥ |ERR2| then ERR1
Else ERR2
PID1 Feedback Output Scaling
(14.058) can then be used to scale the results.
PID1 Feedback Square Root Enable 2
(14.062) can be used in
converting the output of the combined feedback from pressure to flow. It is easier to use a pressure transducer than a flow transducer, and so the
feedback from the transducer needs to be converted from pressure to flow. As flow = Constant x √Pressure the square root function can be used in the
conversion.
Parameter
14.059
PID1 Mode Selector
Short description
Defines the mode of PID1
Mode
Open
‑
Loop
Minimum
0
Maximum
7
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Fbk1
1
Fbk2
2
Fbk1 + Fbk2
3
Min Fbk
4
Max Fbk
5
Av Fbk
6
Min Error
7
Max Error
See
PID1 Feedback Output Scaling
(14.058).
Parameter
14.060
PID1 Feedback Square Root Enable 1
Short description
Enables the squre root function of PID1
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
See
PID1 Feedback Source
(14.004).
Parameter
14.061
PID2 Feedback Square Root Enable
Short description
Enables the squre root function of PID2
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
See
PID1 Feedback Square Root Enable 1
(14.060)
244
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...