Parameter
06.010
Enable Conditions
Short description
Displays all the conditions needed to change the state of the final drive enable
Mode
Open
‑
Loop
Minimum
0
(Display: 000000000000)
Maximum
4095
(Display: 111111111111)
Default
Units
Type
16 Bit Volatile
Update Rate
2ms write
Display Format
Binary
Decimal Places
0
Coding
RO, ND, NC, PT
The Final drive enable is a combination of the
Hardware Enable
(06.029),
Drive Enable
(06.015) and other conditions that can prevent the drive from
being enabled. All of these conditions are shown as bits in
Enable Conditions
(06.010) as given in the table below.
Enable Conditions
(06.010)
bits
Enable condition
0
Hardware Enable
(06.029)
1
Drive Enable
(06.015)
2
0 if auto-tune completed or trip during auto-tune, or if the drive stops when supply loss stop is
active, but the drive needs to be disabled and re-enabled. (Always 1 in Regen mode).
3
1 if fire mode is active.
4
Zero if
Position Feedback Initialized
(03.076) is present and all devices are not indicated as
initialised, otherwise one.
5
Zero until the drive thermal model has obtained temperatures from all drive thermistors at
least once.
6
Zero until all option modules that are present in the drive have indicated that they are ready
to run or the system has timed out waiting for this.
7-10
Zero if an option module has forced the drive to be disabled if for example it is updating its
user program. Bit 7 corresponds to slot 1, bit 8 to slot 2, etc.
11
Zero if the drive is in standby mode. See
Standby Mode Enable
(06.060)
Parameter
06.011
Sequencer State Machine Inputs
Short description
Displays the states of inputs into the sequencer state machine
Mode
Open
‑
Loop
Minimum
0
(Display: 000000)
Maximum
63
(Display: 111111)
Default
Units
Type
8 Bit Volatile
Update Rate
2ms write
Display Format
Binary
Decimal Places
0
Coding
RO, ND, NC, PT, BU
The bits in
Sequencer State Machine Inputs
(06.011) show the state of the inputs to the sequencer state machine as given in the tables below.
Sequencer State Machine Inputs
(06.011)
Signal
Indicates
0
Final drive enable
The drive inverter is allowed to be enabled.
1
Final drive run
The motor can move away from standstill.
2
Under Voltage Active
(10.016)
The under voltage condition has been
detected.
3
Zero Speed
(10.003)
Indicated when the motor has stopped.
4
Drive tripped
The drive is tripped.
5
Supply Loss
(10.015)
Supply loss condition has been detected.
Parameter
06.015
Drive Enable
Short description
Set to 1 to enable the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
1
Units
Type
1 Bit User Save
Update Rate
2ms read
Display Format
Standard
Decimal Places
0
Coding
RW, BU
Drive Enable
(06.015) must be active for the drive to be enabled. See description of enable logic.
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
87
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...