Parameter
11.065
Drive Rating And Configuration
Short description
Displays the drive rating and configuration
Mode
Open
‑
Loop
Minimum
0
(Display: 00000000)
Maximum
99999999
(Display: 99999999)
Default
Units
Type
32 Bit Volatile
Update Rate
Power-up write
Display Format
Lead Zero Pad
Decimal Places
0
Coding
RO, ND, NC, PT
See
Product Identifier Characters
(11.064).
Parameter
11.066
Power Stage Identifier
Short description
Displays the power stage identifiers within the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
255
Default
Units
Type
8 Bit Volatile
Update Rate
Power-up write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT, BU
Power Stage Identifier
(11.066) is used to show power stages that require changes to the drive user parameters (i.e. visibility, range or defaults). It
should be noted that this parameter does not identify the rating of the power stage.
Power Stage Identifier
(11.066)
Power Stage
0
Standard Unidrive M
1
Unidrive M with no braking IGBT
2
Servo drive
Parameter
11.067
Control Board Identifier
Short description
Displays the control board identifiers within the drive
Mode
Open
‑
Loop
Minimum
0.000
Maximum
65.535
Default
Units
Type
16 Bit Volatile
Update Rate
Power-up write
Display Format
Standard
Decimal Places
3
Coding
RO, ND, NC, PT, BU
Control Board Identifier
(11.067) identifies the control board hardware in the form A.BBB. BBB is the hardware identifier from the control board and A
indicates whether this is a standard or high speed product as given in the table below.
A
BBB
Control Board
0
002 or 003
Unidrive M - Standard
1
002 or 003
Unidrive M - High Speed
0
004
Servo
Parameter
11.068
Internal I/O Identifier
Short description
Displays the internal I/O identifiers within the drive
Mode
Open
‑
Loop
Minimum
0
Maximum
255
Default
Units
Type
8 Bit Volatile
Update Rate
Power-up write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT, BU
Internal I/O Identifier
(11.068) identifies the internally fitted I/O option as given in the table below.
Internal I/O Identifier
(11.068)
Internal I/O
0
Analog and digital I/O
1
Digtial only I/O
2
Analogue and digital I/O with additional relay
3
Servo drive I/O
The tables below show which I/O functions are available for each of the internally fitted I/O options.
212
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...