Parameter
01.008
Negative Reference Clamp Enable
Short description
Set to 1 to allow the minimum reference clamp value to be negative
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Minimum Reference Clamp
(01.007).
Parameter
01.009
Reference Offset Select
Short description
Enables the use of the reference offset
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Reference Offset
(01.004).
Parameter
01.010
Bipolar Reference Enable
Short description
Enables the minimum value of the reference to be negative
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW
See
Minimum Reference Clamp
(01.007).
Parameter
01.011
Reference On
Short description
Indicates that the reference from the reference system is active
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
2ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reference On
(01.011), which is controlled by the drive sequencer (see Menu 6) indicates that the reference from the reference system is active. Note that
Reference On
(01.011) is also used in RFC-A and RFC-S modes to enable and disable the
Hard Speed Reference
(03.022).
Parameter
01.012
Reverse Select
Short description
Indicates when the reverse function is active
Mode
Open
‑
Loop
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
2ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Reverse Select
(01.012), which is controlled by the drive sequencer (see Menu 6), is used to invert
Reference Selected
(01.001) or the
Jog Reference
(01.005).
Parameter
01.014
Reference Selector
Short description
Defines the source for the references
Mode
Open
‑
Loop
Minimum
0
Maximum
6
Default
0
Units
Type
8 Bit User Save
Update Rate
4ms read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
24
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
Содержание Powerdrive F300
Страница 1: ...Parameter Reference Guide Powerdrive F300 Open Loop Mode Issue 01 15 00 ...
Страница 20: ...Menu 1 Frequency References Mode Open Loop 20 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 21: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 21 ...
Страница 36: ...Menu 2 Frequency Ramps Mode Open Loop 36 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 108: ...Menu 7 Single Line Descriptions Analog I O Mode Open Loop 108 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 112: ...112 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 144: ...144 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 168: ...Menu 10 Status and Trips Mode Open Loop 168 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...
Страница 231: ...Powerdrive F300 Parameter Reference Guide Issue 01 15 00 231 ...
Страница 232: ...232 Powerdrive F300 Parameter Reference Guide Issue 01 15 00 ...