90 Chapter 7 System Operation And Maintenance
4. Add the sum of the preceding two pressures to find out the saturation temperature corresponding to the saturation
pressure.
The difference between the suction temperature at the sensing bulb and the saturation temperature is the suction
superheat degree. Try to achieve suction superheat between 5k ~ 8k.
Note
The suction superheat degree is critical to the compressor lifespan. If the compressor runs with little or no suction superheat
degree for a long time, slugging may occur to the compressor, damaging the scroll plate of the scroll compressor.
7.6.4 Thermal Expansion Valve
Operation
The auto-regulation of the thermal expansion valve guarantees sufficient refrigerant for the evaporator in order to meet
the needs of the load. The superheat degree is an indicator of the operation state of thermal expansion valve. If the
refrigerant to the evaporator is insufficient, the superheat degree will be high; and if the refrigerant to the evaporator is
too much, the superheat degree will be low. The proper superheat degree is 5k ~ 8k.
Regulation
Follow the following procedures to regulate the superheat degree setting.
1. Unscrew the bonnet at the bottom of the expansion valve.
2. Rotate the rotary switch counter clockwise to reduce the superheat degree.
3. Rotate the rotary switch clockwise to raise the superheat degree.
Note
1. Every time you rotate the rotary switch, do not rotate it for more than one round, and it may take up to 30mins to reach a new
balance.
2. Before delivery, the refrigerant of water-cooled unit has been charged, and the thermal expansion valve position has been
adjusted, so it is recommended not to adjust it on site. If you need to adjust the thermal expansion valve position, please contact
the technical support.
7.6.5 Hot Gas Bypass Valve (For Single Compressor System)
When the heat load in the room is not high, the single compressor system can regulate the indoor temperature by
using the hot gas bypass valve. In this way, the frequent use of the compressor is avoided, and energy saving effect is
realized. The hot gas bypass is shown in Figure 7-5.
进水管路
出水管路
压缩机
板式换
热器
蒸发器
膨胀阀
除湿电磁阀
Dehumidification
solenoid valve
Evaporator
Expansion valve
Hot gas bypass
solenoid valve
BPHE
Compressor
Water flow
regulating valve
Water out pipe
Water in pipe
Figure 7-5 Hot gas bypass solenoid valve
Liebert.PEX2 Series Air Conditioner User Manual