Chapter 5 iCOM Controller 65
Liebert.PEX2 Series Air Conditioner User Manual
Parameters
Default
Setting range
Description
S425
FC FLUSH
0hr
-
Free cooling auto flush time, unit: hr (hour)
S426
HT FLUSH
0hr
-
Hot water auto flush time, unit: hr (hour)
S427 BALL
OFF +0.0bar
-
-
S428 HEAT AS
-
-
-
S429 CW_CTRL -
-
-
S430 MAIN
V
-
-
-
S431 VALV
ROT -
-
-
S432 VALV TIM
-
-
-
S433 DEHUM
OP -
-
-
5.7.10 SERVICE INFO
The SERVICE INFO menu provides the contact information of maintenance personnel. The maintenance personnel
can input and save their contact information through this submenu.
5.8 ADVANCED MENUS
The ADVANCED MENUS include PASSWORD LEVEL, FACTORY SETUP and PASSWORDS, as shown in Figure
5-10.
ADVANCED MENUS1 / 2
PASSWORD LEVEL
FACTORV SETUP
3 ? ?
??
SET
PASSWORDS
2 / 2
ACCESS
ADVANCED MENUS
Figure 5-10 ADVANCED MENUS
5.8.1 PASSWORD LEVEL
It is operated by Emerson service personnel.
5.8.2 FACTORY SETUP
The FACTORY SETUP menu is displayed in nine pages. The parameters are described in Table 5-29 ~ Table 5-38.
Unit code related settings
Table 5-29 Descriptions of unit code related settings
Parameters (1/9)
Default
Setting range
Description
A003
UC 01
0
… …
…
A003
UC 06
0
A005
UC 07
0
… …
…
A005
UC 12
0
A007
UC 13
0
… …
…
A007
UC 18
0
-
Unit code setting. The code has 18 bits. Each bit can be set as 0 ~
20
A008
UC CTRL
No
Save, Load,
Compare, No
Options include:
Save: after UC01 ~ UC18 are changed, the changed can be saved
through the save command.
Load: load parameters to the unit code directly.
Compare: compare the present parameters and the parameters to
be loaded.
No: All changes are cancelled. Keep the old parameters