62 Chapter 5 iCOM Controller
The delay enabling determines whether the alarm will be displayed and the alarm menu is entered, Options include
‘Yes’ and ‘No’.
The alarm type can be set to ‘ALM’ (alarm), ‘WRN’ (warning) and ‘MSG’ (message). They determine the alarm degree
of the corresponding event.
The alarm names are listed in Table 5-25.
Table 5-25 Alarm name description
SN
Alarm/event
name
Description
SN
Alarm/event
name
Description
S236
FOL
Fan overload
S266
LOF
Loss of flow
S237
LOA
Loss of airflow
S267
SGP
Standby glycol pump on
S238
CF
Filter clogged
S268
STB
Standby unit on
S239
HRT
High room temp.
S269
HUP
Humidifier problem
S240
LRT
Low room temp.
S270
NOC
No connection w/Unit1
S241
HRH
High room hum.
S271
-
No connection w/UnitX
S242
LRH
Low room hum.
S272
LOP
LOSS OF POWER
S243
HTA
High temperature of sensor A
S275
CI1
Customized input 1
S244
LTA
Low temperature of sensor A
S276
CI2
Customized input 2
S245
HHA
High humidity of sensor A
S277
CI3
Customized input 3
S246
LHA
Low humidity of sensor A
S278
CI4
Customized input 4
S249
OL1
Compressor 1 overload
S279
CS
Call for service
S250
OL2
Compressor 2 overload
S280
HTD
High temperature
S251
HP1
Compressor 1 high pressure
S281
LB1
Loss of air blower 2
S252
HP2
Compressor 2 high pressure
S282
RL
Reheat lockout
S253
LP1
Compressor 1 low pressure
S283
HL
Humidifier lockout
S254
LP2
Compressor 2 low pressure
S284
FCL
FC lockout
S255
PD1
Compressor 1 pumpdown fails
S285
CL
Compressor(s) lockout
S256
PD2
Compressor 2 pumpdown fails
S288
SC1
Short cycle 1
S257
HT1
Digital scroll 1 high temperature
S289
SC2
Short cycle 2
S258
HT2
Digital scroll 2 high temperature
S290
NOP
NO power
S259
EHO
EL HEAT HIGH TEMP
S291
CN1
Condensor 1 Fail
S262
WHE
Working hours exceeded
S292
CN2
Condensor 2 Fail
S263 SMO Smoke
detected
S293
EFF
EC Fan fail
S264
WUF
Water under floor
S294
HST
High supply air temperature
S265
CPH
Conderser pump high water
S295
LST
Low supply air temperature
5.7.7 CALIBRATION
The CALIBRATION menu can calibrate sensors by setting offsets. The parameters are listed in Table 5-26. The
parameters are in pairs: the former is the calibrated value and the latter is the calculated value, or the sum of the
measured value and the calibrated value. This value is engaged in the calculation of control need.
Table 5-26 Descriptions of CALIBRATION parameters
Parameters
Default
Description
S602 RTN TEMP K
Calibrated return air temperature. It can be set as a positive or negative value. Use the up
and down buttons to change the setting value, 0.1K at each step
S603 CAL TEMP 25°C
Sum of the calibrated value and measured return air temperature. This value is compared
with the setting value as the system actual temperature and is engaged in the calculation
S604 RTN HUM
+0.0%
Calibrated return air humidity. It can be set as a positive or negative value. Use the up and
down buttons to change the setting value, 1% at each step
S605 CAL HUM
44.0%
Sum of the calibrated value and measured return air humidity. This value is compared with
the setting value as the system actual humidity and is engaged in the calculation
S606 DS1 NTC
+0.0K
Calibrated digital scroll 1NTC. It can be set as a positive or negative or positive value. Use
the up and down buttons to change the setting value, 0.1K at each step
S607 CAL DS1
29°C
Sum of the calibrated value and return air humidity measured by digital scroll 1NTC
sensor. This value is engaged in the calculation
S608 DS2 NTC
+0.0K
Calibrated digital scroll 2NTC. It can be set as a positive or negative value. Use the up and
down buttons to change the setting value, 0.1K at each step
Liebert.PEX2 Series Air Conditioner User Manual