64 Chapter 5 iCOM Controller
Liebert.PEX2 Series Air Conditioner User Manual
Parameters
Default
Setting range
Description
S838 GW #1
0
S838 GW #2
0
S838 GW #3
0
S838 GW #4
0
-
Set gateway address
S840 U2U PROT
GBP
-
-
S841
U2U ADD
3
-
Group address No. of this unit
S842 U2U GRP
1
-
-
S843
BL CTRL
No
S + R, No
Boot program variant load. Saving the change of S835 ~ S841 needs
the S + R command of this parameter. The system will reset after the
saving, and configure according to the new parameters
S843
BL STAT
Change
Change, Valid
Indication of whether or not the parameters set through S835 ~ S841
are saved. ‘Change’ means that the parameter is changed but not
saved. ‘Valid’ means that the setting is valid and saved
S844
SR CTRL
No
C + R, No
Static RAM data reset control. If the change of S835 ~ S841 are not
saved, using the C + R command in this parameter can restore S835
~ S841 to their original settings, and the system will reset afterwards
S844 SR STAT
Valid
-
STD
SW#
-
-
Version No. of the control software
MAC
00:00:68:19:
31:70
00:00:68:19:3
1:70
MAC address of the network card of the iCOM controller
NAME UNIT
UNIT
Name of the unit. By default: UNIT. You can change the name as
you need
5.7.9 OPTIONS SETUP
The OPTIONS SETUP menu is used to set the parameters according to the equipment-specific demands. See Table
5-28 for detailed descriptions.
Table 5-28 Descriptions of OPTIONS SETUP parameters
Parameters
Default
Setting range
Description
S402 COMP SEQ
Auto
Auto, 1
(compressor 1
being the
primary one), 2
(compressor 2
being the
primary one)
Compressor sequence. Range: Auto, 1 (compressor 1 being the
primary one), 2 (compressor 2 being the primary one)
S403 LP DELAY
1min
-
Low pressure alarm delay
S405
EL HEAT
1
0 ~ 3
Electric heating stages
S406
EL HEAT C
-
-
-
S407 HW HEAT
No
Yes, No
Hot water heating enabled
S408 ALL HEAT
3
0 ~ 3
heating stages.
S409 LWDconn
No
Yes, No
LWD connected. Range: Yes (water low sensor connected), No
(water low sensor not connected)
S409 V_CTRL
Time
Time, Feedback
-
S410 3P RUN
165s
-
3P actuator runtime
S411 3P DIR
DIR
DIR, REV
3P actuator direction
S413 HUM ENAB
Yes
Yes, No
Humidification enabled
S414 IR FLUSH
150%
-
Infrared flush rate
S415 HUMSTEAM %
-
-
S416
HUM CONT
On, Off
On, Off, Prop
Humidifier control mode
S417 HUM.TIME
s
-
Humidifier bottle flush time
S418 HUM.MAN
Yes
Yes, No
Humidifier bottle manual flush enabled
S419 DEHUM EN
Yes
Yes, No
Dehumidification enabled.
S420 REST EN
Yes
Yes, No
Auto restart enabled
S421 RESTART
s
-
Unit auto restart time
S422 ONOFF EN
Yes
Yes, No
On-off key enabled. If “no” is selected, the ON/OFF key cannot be
used to perform on/off operation on the machine.
S424 CW FLUSH
0hr
-
Cooling water auto flush time, unit: hr (hour)