Chapter 2 Mechanical Installation 21
2.4.4 Installation Procedures
The installation procedures of the indoor unit are as follows:
1. Make a mounting base according to the dimensions in Figure 2-22, Figure 2-23 and Figure 2-24, and the
requirements in Table 2-4. Emerson can supply a range of mounting bases to suit the required height.
2. Lay a layer of rubber cushion on the top, lateral of the mounting base and on the bottom of the steel plate
respectively. See Figure 2-22, Figure 2-23 and Figure 2-24 for their positions and see Table 2-4 for the thickness.
3. Determine the installation position. Fix the mounting base onto the mounting position according to the site
conditions and user’s requirement.
4. Fix the air conditioner cabinet onto the mounting base with nuts, spring washers, flat washers and bolts.
694
850
Installation hole of 4-M8
×
60 sems screw
40
H
75
8
76
4
79
8
893
926
78
100
Rubber cushion (top)
Base
Installation hole of 4-M8 anchor bolt
Rubber cushion (bottom)
Rubber cushion (lateral)
Angle steel
Steel plate
Front side of cabinet
Rear side of cabinet
Figure 2-22 Mounting base appearance and dimensions of one-bay series (unit: mm)