Chapter 5 iCOM Controller 55
SERVICE MENUS 1 / 5
PASSWORD LEVEL
SETPOINTS
0 ? ?
??
C / F
H
%R
SE T
SERVICE MENUS
STANDBY
WELLNESS
2 / 5
WELLNESS
SERVICE MENUS
DIAGNOSTICS
SET ALARMS
SERVICE
ALARMS
SET
3 / 5
4 / 5
CALIERATION
NETWORK SETUP
NETWORK
SERVICE MENUS
5 / 5
OPTIONS SETUP
SERVICE INFO
SET
UP
SERVICE MENUS
Figure 5-8 SERVICE MENUS
5.7.1 PASSWORD LEVEL
It is operated by Emerson service personnel.
5.7.2 SETPOINTS
Different from the SETPOINTS in the USER MENUS, the SETPOINTS in SERVICE MENUS has many more
parameters. See Table 5-11 for the parameter descriptions.
Table 5-11 Descriptions of SETPOINTS parameters
Parameters Default Setting
range
Description
S102
TEMP SET
23°C
5°C ~ 40°C
Temperature setpoint
S103
CTRL TYPE PI
Prop, PI, Intel, No
Control type selection
S104
TEMP PB
7K
2.2K ~ 30K
Temperature proportional band setpoint, or the P in PID control
S105
TEMP INT
min
-
Temperature integration time setpoint, or the I in PID control
S107
AUTOSET
Yes
Yes, No
Autoset enable
S108
TEMP DB
0K
0K~20K
Temperature deadband setting range
S109
2ND SETP
23°C
5°C ~ 40°C
-
S110
BACK TSP
23°C
5°C ~ 40°C
Backup temperature setpoint
S111
HEAT DB
0K
0K~20K
Heaters deadband setting range
S113
HUM SET
50%
1% ~ 80%
Humidity setpoint
S114
HUM CTRL
Pred
Comp, Rel, Pred
Humidity control type
S115
HUM PB
10%
1% ~ 20%
Humidity proportional band
S116
HUM INT
5min
-
Humidity integration time
S117
HUM DB
0%
1% ~ 50%
Humidity deadband setting range
S118
LO LIM 1
k
-
Dehum/Heat low limit 1
S119
LO LIM 2
-1.7K
-5.5K ~ -1.1K
Dehum/Heat low limit 2
S124
SUP SENS
No
No, Lim, Ctrl, Cool
Supply air type
S125
SUP TEMP
5°C
5°C ~ 27°C
Air supply limit temperature setpoint
S126
SUP TYPE
PI
Prop, PI, PID, Intel
Supply control type
S127
SUP PB
12K
2K ~ 30K
Supply proportional band
S128
SUINT
0min
0 ~ 15min
Supply integration
S130
SUP DB
-
0K~20K
Supply deadband
S131
VPULS
5%
0 ~ 10%
Valve Pulse
S132
CF0
-
0.01 ~ 100%
Cooling filter at 0%
S132
CF100
-
0.01 ~ 100%
Cooling filter at 100%
S133
RET CO
0K
0 ~ 10K
Return Compensation
S135
AMB TYPE
No
CONT, EFC, VAL, No
DT between Room/Outdoor Type
S136 AMB
DT
5°C
0
~
20°C
DT between Room Air/Outdoor
S137
FC TYPE
No
No, CONT, VAL
DT between Room/FC Type
S138 FC
DT
4.5°C
0
~
20°C
DT between Room Air/FC Fluid
S139
MIN CW
No
Yes, No
Minimum CW temperature protection selection
S140
MIN CW
7°C
0 ~ 20°C
Minimum CW temperature value
S141
LOCK FC
0°C
0 ~ 9°C
Lockout FC at FC Fluid below
Liebert.PEX2 Series Air Conditioner User Manual