58 Chapter 5 iCOM Controller
Liebert.PEX2 Series Air Conditioner User Manual
Parameters Default
Description
S042
OL AL
0
Number of overload alarms occurred to compressor 2 since the last maintenance
S043
DS HT AL
0
Number of digital scroll high temperature alarms occurred to compressor 2 since the last
maintenance
S044 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HEAT1
Table 5-18 Descriptions of WELLNESS HEAT1 parameters
Parameters
Default
Description
S046
STARTS
-
Number of electric heater 1 starts since the last maintenance
S047
RUN HRS
hr
Electric heater 1 run hours since the last maintenance
S048
AVG RUN
min
Average electric heater 1 run time calculated through the number of starts and run hours
S049
BEST
24
Starts per day best
S050
WORST
240
Starts per day worst
S051
ALARMS
0
Number of high pressure alarms since the last maintenance
S052 BONUS
0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HEAT2
Table 5-19 Descriptions of WELLNESS HEAT2 parameters
Parameters Default
Description
S057
STARTS
-
Number of electric heater 2 starts since the last maintenance
S058
RUN HRS
hr
Electric heater 2 run hours since the last maintenance
S059
AVG RUN
min
Average electric heater 2 run time calculated through the number of starts and run hours
S060
BEST
24
Starts per day best
S061
WORST
240
Starts per day worst
S062
ALARMS
0
Number of high pressure alarms since the last maintenance
S063 BONUS
0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HEAT3
Table 5-20 Descriptions of WELLNESS HEAT3 parameters
Parameters Default
Description
S068
STARTS
-
Number of electric heater 3 starts since the last maintenance
S069
RUN HRS
hr
Electric heater 3 run hours since the last maintenance
S070
AVG RUN
min
Average electric heater 3 run time calculated through the number of starts and run hours
S071
BEST
24
Starts per day best
S072
WORST
240
Starts per day worst
S073
ALARMS
0
Number of high pressure alarms since the last maintenance
S074 BONUS
0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HUM
Table 5-21 Descriptions of WELLNESS HUM parameters
Parameters Default
Description
S079
STARTS
-
Number of humidifier starts since the last maintenance
S080
RUN HRS
hr
Humidifier run hours since the last maintenance
S081
AVG RUN
min
Average humidifier run time calculated through the number of starts and run hours
S082
BEST
24
Starts per day best
S083
WORST
240
Starts per day worst
S084
ALARMS
0
Number of high pressure alarms since the last maintenance
S085 BONUS
0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance