66 Chapter 5 iCOM Controller
Parameters (1/9)
Default
Setting range
Description
A009
UC STAT
OK
Not available,
Invalid, OK,
Changed,
Updating
Unit code status. Range:
Not available: parameters set through UC01 ~ UC18 are
unavailable.
Invalid: parameters set through UC01 ~ UC18 are invalid.
OK: parameters set through UC01 ~ UC18 are effective.
Changed: parameters UC01 ~ UC18 are changed, but not saved.
Updating: parameters are updating
A010
EL CTRL
Load
-
External data can be loaded through the load command
A011
EL STAT
OK
Not available,
Invalid, OK,
Changed,
Updating
Exception list status. Range:
Not available: parameters set through UC01 ~ UC18 are
unavailable.
Invalid: parameters set through UC01 ~ UC18 are invalid.
OK: parameters set through UC01 ~ UC18 are effective.
Changed: parameters UC01 ~ UC18 are changed, but not saved.
Updating: parameters are updating
System related settings
Table 5-30 Descriptions of system related settings
Parameters (2/9)
Default
Setting range
Description
A102
REFRIG
R22
R407C, R22,
R410A
Refrigerant type selection
A103
MOTOR OL
SHUTD
SHUTD,
DISAB
Main fan overload. The action to take after the fan overload. Range:
SHUTD (fan shuts down), DISAB (shut down humidifier, dehumidifier and
heater, only keep the cooling unit running)
A104
AIR LOSS
SHUTD
SHUTD,
DISAB
The action to take after the loss of airflow. Range: SHUTD (fan shuts
down), DISAB (shut down humidifier, dehumidifier and heater, only keep
the cooling unit running)
A105
# COMP
0
0 ~ 2
Number of compressors
A106
COMP DLY
s
-
Compressor delay time
A107
COMP ON
min
0 ~ 5min
Compressor minimum on time
A108
COMP OFF
3min
0 ~ 5min
Compressor minimum off time
A109
PUMPDOWN
Yes
Yes, No
Pump down enable
A110
CAP TYPE
No
4step,
HGBP, DS,
DS + TH, No
Capacity control type. 4step: four steps. HGBP: hot gas bypass. DS:
digital scroll. DS + TH: digital scroll and temperature switch. No: with no
need for capacity control type
A111
FLOCT
0s
0 ~ 180s
Shutdown time of airflow loss
Other settings
Table 5-31 Descriptions of other settings
Parameters (3/9)
Default
Setting range
Description
A113
DS CYCLE
s
-
Digital scroll cycle
A114
DS HT
°C
-
Digital scroll high temperature
A115
DS SWB
°C
-
Digital scroll switchback
A116
LP TYPE
Analog
Analog, Digital
Low pressure device type
A117
LP PH1
ps
-
Low pressure threshold phase 1
A118
LP PH2
ps
-
Low pressure threshold phase 2
A119
LC PRE
0.0s
-
Liquid control pre-time
A120
LC POST
0.0s
-
Liquid control post-time
A121
CHARGE P
bar
-
Loss of Charge Protection
Liebert.PEX2 Series Air Conditioner User Manual