56 Chapter 5 iCOM Controller
Parameters Default Setting
range
Description
S142
TRANS CH
2%
0.1 ~ 100%
Transition Change
S146 FANSPEED Auto
Auto, Man, ECO, SUP,
DELT
VSD Fanspeed
S147
VSD SET
100%
0 ~ 100%
Standard speed of the unit
S148
VSD MIN
60%
0 ~ 100%
Minimum speed of the unit
S149
VSD DEH
60%
0 ~ 100%
Speed used during dehum
S150
VSD NOP
100%
0 ~ 100%
Speed used when CI is active
S151
FF0%
0.2%/s
0 ~ 100%/s
Fanspeed Change (at 0%)
S151
FF100%
1%/s
0 ~ 100%/s
Fanspeed Change (at 100%)
S152
FRD
0s
0 ~ 300s
Fanspeed Reposition Delay
S153 HAD
-
-
-
S154
HAP
6°C
2 ~ 30°C
Fanspeed P-Band
S155
HAI
5min
0 ~ 15min
Fanspeed Integration
S157 SCR
TYPE -
-
-
S158 CO1
ON
-
-
-
S159 CO1
OFF -
-
-
S160 CO1
TD
-
-
-
S161 CO2
ON
-
-
-
S162 CO2
OFF -
-
-
S163 CO2
TD
-
-
-
S164 CYCLET
-
-
-
S165 SCR
FACT -
-
-
S166 ACT
SCR -
-
-
5.7.3 STANDBY
The parameters of the STANDBY menu are described in Table 5-12.
Table 5-12 Descriptions of STANDBY parameters
Parameters
Default Setting range
Description
S502
#STANDBY 1
0 ~ 32
Number of standby units
S503 ROTATION Daily
No, Daily,
MON ~ SUN,
M - MON ~ M
- SUN
Rotation frequency setting of the running and standby units. Range:
Daily: rotate once a day.
MON ~ SUN: rotate once a week. The rotation occurs on Monday ~ Sunday
of the week. For example, MON means rotation occurs on Monday of every
week.
M - MON ~ M - SUN: rotate once a month. The rotation occurs on Monday ~
Sunday of the first week of the month. For example, M - MON means rotation
occurs on Monday of the first week of every month
S504
ROT HOUR
hr
-
Used to set the hour of the detailed time while rotation
S505
ROT MIN
min
-
Used to set the minute of the detailed time while rotation
S506
ROT BY
1
1 ~ 8
The unit number for a rotation
S507
DO ROT
No
Yes, No
Perform one rotation
S508 CASCADE No
CO/HE,
Cool, Yes,
No
Cascade function selection. ‘Yes’ corresponds to temperature and humidity
control and ‘no’ corresponds to closing the cascade
S509
STBY HT
No
Yes, No
Whether to start all standby units upon high temperature alarm
5.7.4 WELLNESS
The iCOM controller calculates the bonus and penalty over the equipment maintenance based on the parameters in
the WELLNESS menu and the equipment operation historical data, so as to find out the next system maintenance
time.
Informing the maintenance personnel of the maintenance time makes the air conditioner run in the optimal mode,
which reduces the chances of faults and raises the system reliability.
The WELLNESS menu includes nine groups of parameters, including WELLNESS BASICs, and WELLNESS MOTOR,
WELLNESS COMPs, WELLNESS HEATs and WELLNESS HUM. See Table 5-13 ~ Table 5-21 for detailed parameter
descriptions.