68 Chapter 5 iCOM Controller
Analog output related settings
Table 5-35 Descriptions of analog output related settings
Factory 7/9
Default
Setting range
Description
A157 ANOUT1LO
0%
0 ~ 100%
A157 ANOUT1HI
100%
0 ~ 100%
A158 ANOUT2LO
0%
0 ~ 100%
A158
ANOUT2HI
100%
0 ~ 100%
A159
ANOUT3LO
0%
0 ~ 100%
A159
ANOUT3HI
100%
0 ~ 100%
A160
ANOUT4LO
0%
0 ~ 100%
A160
ANOUT4HI
100%
0 ~ 100%
A161
FS HE/HU
100%
0 ~ 100%
-
A163
ANOUT1 No
-
A164
ANOUT2 No
-
A165
ANOUT3 No
-
A166
ANOUT4 No
-
Analog output selection. See Table 5-36
Table 5-36 Descriptions of analog output options
Options Description
Options
Description
CW010
CW/FC 0 ~ 10V
ALBD2
AlarmBoard 2
HW Hot
water
ALBD3
AlarmBoard
3
HW175
Hot water 1.75
IVAR
I-Variex 1
VSD
Variable fan speed drive
HUM%
HT HUM
COOL Cooling
SUP
Supply
Temperature
CV175 CW/FC
1.75
RET
Return
Temperature
COOL1 Cooling
1
HUMI
Humidifier
COOL2 Cooling
2
SUPSA
Supersaver
HEAT Heater
INVCO
Inverted
Cool
No
No use
HEAT3
Heating 33%
MBV1
Motorized ball vavle1
CW210
CW/FC 2 ~ 10V
MBV2
Motorized ball vavle 2
C2010
CW2 0 ~ 10V
SCR
Silicon controlled rectifier
C2175
CW2 1.75
CONF
Configurable
C2210
CW2 2 ~ 10V
ALBD1 AlarmBoard
1
Analog action related settings
Table 5-37 Descriptions of analog action related settings
Parameters (8/9)
Default
Setting range
Description
A168
AO1 STA
0%
0% ~ 100%
Analog output 1 start percentage
A168
AO1 STA
0V
0V ~ 10V
Analog output 1 start voltage
A169
AO1 END
100%
0% ~ 100%
Analog output 1 end percentage
A169
AO1 END
10V
0V ~ 10V
Analog output 1 end voltage
A170
AO2 STA
0%
0% ~ 100%
Analog output 2 start percentage
A170
AO2 STA
0V
0V ~ 10V
Analog output 2 start voltage
A171
AO2 END
100%
0% ~ 100%
Analog output 2 end percentage
A171
AO2 END
10V
0V ~ 10V
Analog output 2 end voltage
A172
AO3 STA
0%
0% ~ 100%
Analog output 3 start percentage
A172
AO3 STA
0V
0V ~ 10V
Analog output 3 start voltage
A173
AO3 END
100%
0% ~ 100%
Analog output 3 end percentage
A173
AO3 END
10V
0V ~ 10V
Analog output 3 end voltage
A174
AO4 STA
0%
0% ~ 100%
Analog output 4 start percentage
A174
AO4 STA
0V
0V ~ 10V
Analog output 4 start voltage
A175
AO4 END
100%
0% ~ 100%
Analog output 4 end percentage
A175
AO4 END
10V
0V ~ 10V
Analog output 4 end voltage