E300 Installation and Commissioning Guide
99
Issue Number: 1
If the data is being transferred to the drive with different voltage or current rating a 'Card Rating' trip will occur. The following drive rating dependant
parameters (RA coding bit set) will not be transferred to the destination drive from a NV Media Card when the voltage rating of the destination drive is
different from the source drive and the file is a parameter file. However, drive rating dependent parameters will be transferred if only the current rating
is different. If drive rating dependant parameters are not transferred to the destination drive they will contain their default values.
•
Parameter Cloning
(
N01
)
= Read (1)
- Reading from the NV Media Card.
Setting
Parameter Cloning
(
N01
)
modes to Read (1) and resetting the drive will transfer parameters from the NV Media Card to the drive parameters
and the drive EEPROM, i.e. this is equivalent to writing 6001 to Pr
mm00
. Once the parameters are successfully copied this parameter is
automatically reset to None (0). Parameters are saved to the drive EEPROM after this action is complete.
5.17.2 Auto saving drive parameter changes
•
Parameter Cloning
(
N01
)
= Auto (3)
This setting causes the drive to automatically save any changes made to User Menu A parameters in the drive to the NV Media Card. If the NV Media
Card data block already contains information it is automatically overwritten.
Changing
Parameter Cloning
(
N01
)
to Auto (3) and resetting the drive will immediately save the complete parameter set from the drive to the NV
Media Card. Once the whole parameter set is stored only the individual modified User Menu A parameter setting is updated. At power up, if
Parameter Cloning
(
N01
)
is set to Auto (3), the drive will save the complete parameter set to the NV Media Card.
Advanced parameter changes are only saved to the NV Media Card when Pr
mm00
is set to 'Save Parameters' or 1000 and the drive reset.
If the NV Media Card is removed when
Parameter Cloning
(
N01
) is set to 3
Parameter Cloning
(
N01
) is then automatically set to None (0).
When a new NV Media Card is installed
Parameter Cloning
(
N01
) must be set back to Auto (3) by the user and the drive reset so the complete
parameter set is rewritten to the new NV Media Card if auto mode is still required.
When
Parameter Cloning
(
N01
) is set to Auto (3) the setting of
Parameter Cloning
(
N01
) itself is saved to the drive EEPROM but not the NV Media
Card.
5.17.3 Boot from the NV Media Card on every power up
•
Parameter Cloning
(
N01
)
= Boot (4)
- Boot from NV Media Card on every power up
When
Parameter Cloning
(
N01
) is set to Boot (4) the drive operates the same as Auto mode, except when the drive is powered-up the parameters are
automatically transferred to the drive at power up if the following are true:
•
An NV Media Card is inserted in the drive
•
Parameter data block 1 exists on the NV Media Card
•
The data in block 1 is type 1 to 4 as defined in
Media Card File Type
N04
)
•
Parameter Cloning
(
N01
) on the NV Media Card set to Boot (4)
The drive will display 'Booting Parameters during this operation. If the drive mode is different from that on the NV Media Card the drive gives a 'Card
Drive Mode' trip and the data is not transferred.
If 'Boot' mode is stored on the copying NV Media Card this makes the copying NV Media Card the master device. This provides a very fast and
efficient way of re-programming a number of drives.
'Boot' mode is saved to the NV Media Card but when the NV Media Card is read,
Parameter Cloning
(
N01
) is not transferred to the drive.
•
Pr
mm00 = 2001
It is possible to create a bootable parameter data block by setting Pr
mm00
to 2001 and carrying out a drive reset. This data block is created in one
operation and is not updated when further parameter changes are made. Setting Pr
mm00
to 2001 will overwrite the data block 1 on the NV Media
Card if it already exists.
5.17.4 Comparing drive parameter set to NV Media Card
•
8yyy
- Comparing drive parameter set to NV Media Card
Setting 8yyy in Pr
mm00
, will compare the NV Media Card file with the data in the drive. If the compare is successful Pr
mm00
is simply set to 0. If the
compare fails a 'Card Compare' trip is initiated.
Parameter number
Description
B15
Symmetrical Current Limit
B02
Rated Current
B03
Rated Voltage
B04
Rated Power Factor
B34
Stator Resistance
B13
Maximum Switching Frequency
B34
Transient Inductance
B36
Stator Inductance
D18
Injection Braking Level
O11
Standard Under Voltage Threshold
O14
Low Under Voltage Threshold
Содержание E300 Series
Страница 211: ......
Страница 212: ...0479 0005 01 ...