E300 Installation and Commissioning Guide
93
Issue Number: 1
•
Parameter editing
If the
up and down
keys are pressed together in parameter edit mode, where the value is flashing, then the value of the parameter
being edited will be set to 0 or the minimum value selectable for the given parameter.
If the
left and right
keys are pressed together in parameter edit mode, where the value is flashing, the least significant digit in the parameter
value furthest right) will be selected for editing.
The navigation keys can only be used to move between menus if
User Security Status
(
H02
) has been set to show 'All Menus'.
5.8 Saving parameters
When changing a parameter in User Menu A, the new value is saved when pressing the
Enter button to return to parameter view mode from
parameter edit mode.
If parameters have been changed in the advanced menus, then the change will not be saved automatically. A save function must be carried out.
Procedure
1. Select ‘Save Parameters'* in Pr
mm00
(alternatively enter a value of 1000* in Pr
mm00
)
2. Either:
•
Press the red
reset button
•
Toggle the reset digital input
* If the drive is in the under voltage state (i.e. when the control terminal 1 & 2 are being supplied from a low voltage DC supply) a value of 1001 must
be entered into Pr
mm00
to perform a save function.
5.9 Restoring parameter defaults
Restoring parameter defaults by this method saves the default values in the drives memory.
User Security Status
(
H02
) and
User Security Code
(
H01
) are not affected by this procedure.
Procedure
1. Ensure the drive is not enabled, i.e. the Safe Torque Off (STO), Drive enable on terminal 31 is open or Off (0)
2. Select 'Reset 50 Hz Defs' or 'Reset 60 Hz Defs' in Pr
mm00
(alternatively, enter 1233 (50 Hz settings) or 1244 (60 Hz settings) in Pr
mm00
).
3. Either:
•
Press the red
reset button
•
Toggle the reset digital input
5.10 Displaying destination parameters only
By selecting 'Destinations' in Pr
mm00
(Alternatively enter 12001 in Pr
mm00
), the only parameters that will be visible to the user will be destination
parameters. This function does not require a drive reset to become active. In order to deactivate this function, return to Pr
mm00
and select 'No
action' (alternatively enter a value of 0).
Please note that this function can be affected by the access level enabled, refer to section 5.4
5.11 Displaying non default parameters
The keypad has an option to display all parameters which have been changed from their default values. By selecting 'Show non-default' in Pr
mm00
(or alternatively, enter 12000 in Pr
mm00
), the only parameters that will then be visible to the user will be those containing a non-default value. This
function does not require a drive reset to become active. To deactivate this function, return to Pr
mm00
and select 'No action' or (alternatively enter a
value of 0 in Pr
mm00
).
This function can be affected by the parameter access level selected refer to section 5.4
NOTE
NOTE