204
E300 Installation Guide
Issue Number: 1
Power Comms
Communication has been lost / errors detected between power, control and rectifier modules
90
A Power Comms trip indicates a communications problem within the power system of the drive. The reason for the trip can
be identified by the sub-trip number.
Recommended actions:
•
Hardware fault - contact the supplier of the drive.
Power Down Save
Power down save error
37
The Power Down Save trip indicates that an error has been detected in the power down save parameters saved in non-
volatile memory.
Recommended actions:
•
Perform a 1001 save in Pr
mm00
to ensure that the trip doesn’t occur the next time the drive is powered up.
PSU
Internal power supply fault
5
The PSU trip indicates that one or more internal power supply rails are outside their limits or overloaded.
Recommended actions:
•
Remove keypad from the drive and perform a reset
•
Remove any option modules and perform a reset
•
Remove encoder connection and perform a reset
•
Hardware fault within the drive – return the drive to the supplier
PSU 24V
24V internal power supply overload
9
The total user load of the drive and option modules has exceeded the in 24 V power supply limit. The user load
consists of the drive digital outputs and main encoder supply.
Recommended actions:
•
Reduce the load and reset the drive
•
Remove control connections from the drive and perform a reset
•
Remove any option modules and perform a reset
•
Remove encoder connection and perform a reset
•
Provide an ex 24 V power supply on Control Terminal 2 of the drive
•
Permanent trip, hardware fault within the drive – return the drive to the supplier
Resistance
Measured resistance has exceeded the parameter range
33
The Resistance trip indicates that the measured motor stator resistance during an autotune test has exceeded the
maximum possible value allowable for the drive in
Stator Resistance
(
B34
)
Recommended actions:
•
Check the motor phase to phase resistance at the drive terminals
•
Check the motor phase to phase resistance at the motor terminals
•
Ensure the drives output stator resistance measurement for the motor falls within the range of the drive model
•
Check the motor power cable connections
•
Check the integrity of the motor stator winding using a insulation tester
•
Select a suitable drive model for the motor
•
Replace the motor
Slot App Menu
Application menu Customization conflict error
216
The Slot App Menu trip indicates that more than one option slot has requested to customize the application menus S, T and
U. The sub-trip number indicates which option slot has been allowed to customize the menus.
Recommended actions:
•
Ensure that only one of the Application modules is configured to customize the application menus S, T and U.
Trip
Diagnosis
Type of drive
xx
y
zz
Single power
module system
01
Rectifier number
00: Excessive communications errors detected by the
rectifier module
Source
xx
y
zz
Description
Control
system
00
0
00
Internal power supply overload.
Power
system
01
Rectifier
number
Содержание E300 Series