E300 Installation Guide
205
Issue Number: 1
SlotX Different
Option module in option slot X has changed
204
209
214
The SlotX Different trip indicates that the option module in option slot X on the drive is a different type to that installed when
parameters were last saved on the drive. The reason for the trip can be identified by the sub-trip number.
Recommended actions:
•
Check the currently installed option module is correct
•
Check the option module parameters are set correctly and perform a user save in Pr
mm00.
To inspect / change option module turn Off the AC power supply, ensure the correct option modules are installed in
the correct option module slots and then re-apply the AC power supply
SlotX Error
Option module in option slot X has detected a fault
202
207
212
The SlotX Error trip indicates that the option module in option slot X on the drive has detected an error. The reason for the
error can be identified by the sub-trip number.
Recommended actions:
•
See the relevant
Option module User guide
for details of the trip and sub-trip number
SlotX HF
Option module X hardware fault
200
205
210
The
SlotX HF
trip indicates that the option module in option slot X on the drive has indicated a hardware fault. The possible
causes of the trip can be identified by the sub-trip number.
Recommended actions:
•
Ensure the option module is installed correctly
•
Replace the option module
•
Replace the drive
SlotX Not Fitted
Option module in option slot X has been removed
203
208
213
The SlotX Not Fitted trip indicates that the option module in option slot X has been removed since the last power up.
Recommended actions:
•
Ensure the option module is installed correctly.
•
Re-install the option module.
•
To confirm that any removed option module is no longer required perform a save function in Pr
mm00
.
Soft Start
Soft start relay failed to close, soft start monitor failed
226
The Soft Start trip indicates that the soft start relay in the drive failed to close or the soft start monitoring circuit has failed.
Recommended actions:
•
Hardware fault – Contact the supplier of the drive
Trip
Diagnosis
Sub-trip
Reason
1
No module was installed previously
2
A module with the same identifier is installed, but the set-up menu for this option slot has been
changed, and so default parameters have been loaded for this menu.
3
A module with the same identifier is installed, but the applications menu for this option slot has been
changed, and so default parameters have been loaded for this menu.
4
A module with the same identifier is installed, but the set-up and applications menu for this option slot
have been changed, and so default parameters have been loaded for these menus.
>99
Shows the identifier of the module previously installed.
Sub-trip
Reason
1
The module category cannot be identified
2
All the required customized menu table information has not been supplied or the tables supplied are corrupt
3
There is insufficient memory available to allocate the comms buffers for this module
4
The module has not indicated that it is running correctly during drive power-up
5
Module has been removed after power-up or it has stopped working
6
The module has not indicated that it has stopped accessing drive parameters during a drive mode change
7
The module has failed to acknowledge that a request has been made to reset the drive processor
8
The drive failed to correctly read the menu table from the module during drive power up
9
The drive failed to upload menu tables from the module and timed out (5 s)