C6.1.10/0118-0318/E
46
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
F29
EOE
Differential between the vapour inlet and the vapour
outlet temperature for R507
0.0 to 25.5°C
Not applicable
N.V.
F30
dU0
Differential between the vapour inlet and the vapour
outlet temperature for R134a
0.0 to 25.5°C
Not applicable
N.V.
F31
dU1
Differential between the vapour inlet and the vapour
outlet temperature for R22
0.0 to 25.5°C
Not applicable
N.V.
F32
dU2
Differential between the vapour inlet and the vapour
outlet temperature for R407C
0.0 to 25.5°C
Not applicable
N.V.
F33
dU3
Differential between the vapour inlet and the vapour
outlet temperature for R407A
0.0 to 25.5°C
Not applicable
N.V.
F34
dU4
Differential between the vapour inlet and the vapour
outlet temperature for R407F
0.0 to 25.5°C
Not applicable
N.V.
F35
dU5
Differential between the vapour inlet and the vapour
outlet temperature for R448A
0.0 to 25.5°C
Not applicable
N.V.
F36
dU6
Differential between the vapour inlet and the vapour
outlet temperature for R449A
0.0 to 25.5°C
Not applicable
N.V.
F37
dU7
Differential between the vapour inlet and the vapour
outlet temperature for R410A
0.0 to 25.5°C
Not applicable
N.V.
F38
dU8
Max DLT temperature before changing from vapour
to liquid injection control
-40°C to 180°C
Not applicable
N.V.
F39
dU9
Differential before resuming vapour injection
0.0°C to 25.5°C
Not applicable
N.V.
F40
ULt
Max open EXV warning time
0 to 255 min
2
L2
F41
Uth
Delta between setpoint and shortage of refrigerant
error during max open warning
0.0°C to 25.5°C
8
L2
F42
Eot
Constant liquid temperature mode enabled for low
ambient EVI injection
No (0-NO) - Yes (1-YES)
Not applicable
N.V.
F43
Eod
Constant liquid temperature setpoint
-40°C to 110°C
Not applicable
N.V.
F44
EcM
Constant liquid temperature enable temperature
-40°C to 110°C
Not applicable
N.V.