12
C6.1.10/0118-0318/E
The unit will be turned on for the minimum run time when the low-pressure input is closed.
If the pressure drops below the cut-out value or the low-pressure input opens, the unit should
continue to run for the remaining minimum on time (
C14/LAS
) or until a satisfactory condenser
pressure is reached (
C13/LAd
).
If a suction pressure transducer is present and the suction pressure falls below a given value
(
C15/LAT
) during the minimum on time (
C14/LAS
), then disregard the timer and shut the
compressor off to protect against vacuum operation.
NOTE: For additional features please contact your local Application Engineering
representative.
2.11 XCM25D Electronic controller
– Programming
CAUTION
Low refrigerant charge! Compressor damage!
Never energize the
unit/controller without minimum refrigerant system charge. There is a risk of
malfunction of the controller in deep vacuum operation which can cause
compressor damage.
2.11.1 Programming the local display
Figure 9: Local display
LED
Mode
Function
On
Compressor 1 enabled
Flashing
Anti-short cycle delay enabled
On
Condensing fans enabled
On
Bar display
Flashing
Programming mode
On
PSI display
Flashing
Programming mode
On
When browsing the service menu
Flashing
In fast access menu
On
When browsing the alarm menu
Flashing
A new alarm occurred
On
An alarm is occurring
On
Digital unloader solenoid On
On
In defrost
Table 10: LED functions description
NOTE: By default, the local display will show the value of the suction pressure during
operation. This can be changed by choosing another value for parameter B03/Lod (Remote
Display visualization).