![Emerson Copeland EazyCool ZXDI Series Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/emerson/copeland-eazycool-zxdi-series/copeland-eazycool-zxdi-series_application-manuallines_103132044.webp)
C6.1.10/0118-0318/E
39
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
B03
Lod
Remote display visualization
P1 (0-P1) - P2 (1-P2) - P3 (2-P3) -
P4 (3-P4) - P5 (4-P5) - P6 (5-P6) -
P7 (6-P7)
– Per (7-PER) – Aou (8-AOU)
P1
L2
B04
FiL
Filter enabling for probe reading
n (0-NO) - Y (1-YES)
YES
N.V.
B05
FiC
Coefficient for probe reading filter (0 = max,100 =
disable)
0 to 100, mEd (101)
50
N.V.
C03
Cin
Minimum setpoint for suction pressure/temperature
P1i to US; -50.0°C to US
0.6
L2
C04
CoU
Maximum setpoint for suction pressure/temperature
LS to P1E; LS to 60.0°C
7.2
L2
C05
LS
Compressor regulation probe selection
NU (0-NU)
Suction pressure probe (1-SUP)
Case temperature (2-CST)
Suction pressure switch (3-dIS)
Suction pressure probe
L2
C06
US
EXV closing time before compressor off
0 to 999 sec
0
L2
C07
CPb
Refrigerant selection for regulation
R404A (0-404) - R507 (1-507) -
R134a (2-134) - R22 (3-R22)
–
R407C (4-07C) - R407A (5-07A) -
R407F (6-07F)
– R448A (7-48A) -
R449A (8-49A) - R410A (9-410)
R404A
L1
C08
CoM
Setpoint offset
NU (0-NU)
Small offset (1-SOF)
Medium offset (2-MOF)
Large offset (3-LOF)
LAO (4-FOF)
Not used
L2
C09
rEF
Ambient temperature operation setpoint
-40°C to 110°C
-20
L2
C10
SPo
Pressure/Temperature operation for ambient
differential
0.0 to 9.9 bar; 0.0 PSI to 99.9 PSI
0.0°C to 25.5°C
1
L2
C11
LAI
Ambient temperature recover differential
0.1°C to 25.5°C
5
L2
C12
LAO
Ambient temperature threshold for low ambient
operation
-40°C to 110°C
-10
L2
C13
LAd
Temperature/Pressure to end low ambient timer and
resume normal operation
-40°C to 110°C
-1.5 to 99.9 bar; -21 to 999 PSI
10
L2
C14
LAS
Compressor minimum on time in low ambient
operation
0 to 255 sec
10
L2
C15
LAT
Pressure to end low ambient timer and shut off the
compressor
-1.5 to 99.9 bar; -21.0 to 999 PSI
0.5
L2