C6.1.10/0118-0318/E
50
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
H03
tLS
Voltage sensing 1
no; yes
NO
L2
H04
CS1
Voltage sensing 2
no; yes
NO
L2
H05
CS2
Voltage sensing 3
no; yes
NO
L2
H06
US1
Voltage and current protection enabled
no; yes
YES
L2
H07
US2
Maximum continuous current limit
3PE = 0: 0.0 to 70.0 A
3PE = 1: 0.0 to 35.0 A
Unit dependent
L2
H08
US3
Voltage/current sensing trip minimum off time
0 to 255 min
5
L2
H09
CSE
Adjustable current limit before trip
0.0 to MCC Ampere
9.5
L2
H10
MCC
Ignore current sensing duration at start-up duration
0 to 255 sec
3
L2
H11
dMC
Number of over current trips before lock
0 to 15
5
L2
H12
MC2
Number of loss of phase trips before lock
0 to 15
5
L2
H13
diC
Minimum voltage to trip compressor
0 to 400V
360
N.V.
H14
oCn
Maximum voltage to trip compressor
0 to 800V
480
N.V.
H15
PEn
Over or under voltage minimum time
0 to 255 sec
60
L2
H16
LUo
Compressor minimum off time because of voltage
error
0 to 255 min
3
L2
H17
HUo
Number of compressor trips before lockout because
of voltage
0 to 15
5
L2
H18
dUA
Adjustable under average voltage percentage
0 to 100%
90
L2
H19
Uot
Generate warning or shut down compressor when
phase imbalance
0: Generate warning (0-ARN)
1: Unit off(1-Off)
Unit off
L2
H20
Utn
Missing current duration before warning
0 to 255 sec
10
L2
H21
PiP
Minimum high side superheat
-40 to 110°C
10
L2
H22
PiC
Amount of time allowed in an interval to check for
floodback
0 to H23 min
30
L2
H23
CMd
Interval to check for floodback
H22 to 120 min
45
N.V.
H24
LHS
Duration of checking anti-floodback alarm reset
condition
1 to 255 min
20
N.V.
H25
tFb
Three-phase enable
no; yes
YES
L2
I01
iFb
Ambient temperature threshold to off crankcase
heater
-40°C to 180°C
10
L2