![Emerson Copeland EazyCool ZXDI Series Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/emerson/copeland-eazycool-zxdi-series/copeland-eazycool-zxdi-series_application-manuallines_103132035.webp)
30
C6.1.10/0118-0318/E
4.5 Checks before starting & during operation
IMPORTANT
Liquid valves not fully opened! Liquid trap!
Both valves should be fully
opened on the liquid line, in order to avoid trapping liquid.
▪
Check that all valves are fully opened.
▪
Set the essential parameters of the electronic controller in programming level 1 (refrigerant
type, compressor cut-out/cut-in settings, fan setpoint
….) according to the required
application.
▪
Emerson recommends to check the oil level in the compressor after starting and operation
conditions have stabilised, and to add oil if needed to ensure a sufficient oil level (halfway
up the sight glass).
Содержание Copeland EazyCool ZXDI Series
Страница 1: ...Copeland EazyCool Indoor Condensing Units ZXDI Range Application Guidelines ...
Страница 5: ......