C6.1.10/0118-0318/E
37
Appendix 4: Parameter list Level 1 & Level 2 (Pr1 & Pr2)
Legend
L1 = Parameter in Level 1 (without password)
L2 = Parameter in Level 2 (with password = 3 2 1)
N.V. = Parameter not accessible
NOTE: When changing parameter C05 (LS) a reset of the controller (interruption of power supply) is required.
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
A01
P1C
Probe P1 configuration
Not used (0-NU)
Suction pressure (0-5V)(1-SUP)
Suction pressure (0-
5V)
L2
A02
P1i
Start of scaling for probe 1 (0-5V)
0-5V: -1.5 bar to P1E; -21 PSI to P1E
0
L2
A03
P1E
End of scaling for probe 1 (0-5V)
0-5V: P1i to 99.9 bar; P1i to 999 PSI
15
L2
A04
P1F
Probe P1 calibration
0-5V: -12.0 to 12.0 bar; -12.0 to12.0 PSI
0
L2
A05
P1d
Probe P1 reading error delay (P1C=0-5V)
0 to 255 min
5
L2
A06
P2C
Probe P2 configuration
Not used (0-NU)
Mid coil temperature (NTC10K)(1-MCT)
Mid coil pressure (0-5V)(2-MCP)
Mid-coil pressure (0-
5V)
L2
A07
P2i
Start of scaling for probe 2
0-5V: -1.5 bar to P2E; -21 PSI to P2E
NTC10K: -40°C to P2E
0
L2
A08
P2E
End of scaling for probe 2
0-5V: P2i to 99.9 bar; P2i to 999 PSI
NTC10K: P2i to 110°C
35
L2
A09
P2F
Probe P2 calibration
0-5V: -12.0 to 12.0 bar; -12.0 to 12.0 PSI
NTC10K: -12°C to 12°C
0
L2
A10
P2d
Probe P2 reading error delay (P2C=0-5V)
0 to 255 min
0
L2
A11
P3C
Probe P3 configuration
Not used (0-NU)
Discharge line temperature (1-DLT)
Discharge line
temperature
L2
A12
P3F
Probe P3 calibration
-12°C to 12°C
0
L2
A13
P4C
Probe P4 configuration
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
Not used
L2