![Emerson Copeland EazyCool ZXDI Series Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/emerson/copeland-eazycool-zxdi-series/copeland-eazycool-zxdi-series_application-manuallines_103132049.webp)
C6.1.10/0118-0318/E
44
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
E38
HT9
Fan setpoint modulation enabling
No (0-NO) - Yes (1-YES)
NO
L2
E39
HP9
Condenser temperature setpoint when fan setpoint
modulation is disabled
-40°C to 110°C
27
L1
E40
FSM
Minimum condenser temperature setpoint
-40°C to 110°C
10
L2
E41
FSP
High ambient fan motor override enabled
No (0-NO) - Yes (1-YES)
YES
L2
E42
MCS
High ambient fan motor override differential
0.1°C to 25.5°C
5
L2
E43
FAE
High DLT fan motor override enabled
No (0-NO) - Yes (1-YES)
YES
L2
E44
FAd
High DLT fan motor override differential
-40°C to 180°C
120
L2
E45
FdE
Minimum fan motor speed
0 to 100%
40
N.V.
E46
FdS
Regulation band of variable fan
0.1°C to 25.5°C
10
L1
E47
MSF
Integration time for fan
0 to 999 sec
500
L2
E48
Fbd
Fan full speed duration at fan start-up
0 to 255 sec
0
L2
E49
inF
Fan minimum on time
0 to 255 sec
5
L2
E50
FFS
Fan minimum off time
0 to 255 sec
10
L2
E51
FCn
Fixed condenser fan setpoint
-40°C to 110°C
23
L2
E52
FCF
Fan 1 differential
0.1°C to 25.5°C
7
L2
E53
SF1
Fan 1 to fan 2 differential
0.1°C to 25.5°C
10
L2
E54
HF1
Fan 2 differential
0.1°C to 25.5°C
7
L2
E55
SFD
Fan control with ambient sensor - Min ambient
-40°C to E56
0
L2
E56
HF2
Fan control with ambient sensor - Max ambient
E55 to 110°C
20
L2
E57
FoL
Fan speed control with ambient sensor
0 to 100%
60
L2
E58
FoH
Condenser temperature/pressure threshold for high
alarm
-40°C to 110°C
-1.5 to 99.9 bar; -21 to 999 PSI
27.8
L2
E59
FoM
High condenser temperature alarm delay
0 to 255 min
0
L2
E60
AU2
High condenser temperature alarm with compressor
off
No (0-NO) - Yes (1-YES)
YES
L2
E61
Ad2
Condenser temperature/pressure threshold for alarm
recovery
-40°C to E58°C
-1.5 to E58 bar; -21 to E58 PSI
23
L2
F01
Ab2
Liquid injection setpoint
-40°C to 180°C
Not applicable
N.V.
F02
AH2
Max DLT temperature before full open injection
LIS°C to 180°C
Not applicable
N.V.
Содержание Copeland EazyCool ZXDI Series