C6.1.10/0118-0318/E
51
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
I02
dFb
Compressor minimum off time before turning on the
crankcase heater
0 to 255 min
5
L2
L01
3PE
Steps for initial regulation
SH2 to SH1 steps
15
L2
L02
iMb
Superheating setpoint
0.0°C to 25.5°C
5
L2
L03
CcA
Threshold of low superheating
0.0 to SH18°C
1
L2
L04
CcT
Threshold of high superheating
SH17 to 80.0°C
15
L2
L05
iSt
Extra % of valve close in case of low superheating
0 to 100%
0
L2
L06
SSH
Delay high superheating
0 to 255 sec
30
L2
L07
LSH
Delay low superheating
0 to 255 sec
30
L2
L08
HSH
Threshold of MOP
SH23 to 60.0°C
35
L2
L09
LSP
Threshold of LOP
-50°C to SH22°C
-20
L2
L10
HSd
Activation delay MOP
0 to 255 sec
1
L2
L11
LSd
Activation delay LOP
0 to 255 sec
1
L2
L12
MoP
Steps close/open in case of MOP/LOP
0 to SH1 steps
20
L2
M01
LoP
Max step valve
SH2 to 800 steps
250
L2
M02
dMP
Min step valve
0 to SH1 steps
0
L2
M03
dLP
Extra steps of valve close
0 to 100 steps
20
L2
M04
ASt
Relax steps
0 to 100 steps
0
L2
M05
HSt
Step rate
10 to 100 steps
35
L2
M06
LSt
Regulation of the valve 0: automatic, 1: manual
Automatic (0-AUT)
Manual (1-MAN)
Automatic
L2
M07
ESt
Steps if manual regulation
SH2 to SH1 steps
15
L2
M08
rSt
Proportional band (if 0 the regulation is auto
adaptive)
0 to 50°C
0
L2
M09
Sr
Integral time
0 to 255 sec
20
L2
M10
ErM
Derivative
0 to 255 sec
0
L2
M11
MSt
Dead band
0 to10°C
1
L2
M12
EPb
Min % of the valve
0 to SH15
0
L2
M13
inE
Max % of the valve
SH14 to 100
100
L2
M14
dEr
Filter on the pressure
1 to 255 sec
1
L2