C6.1.10/0118-0318/E
41
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
D05
CoF
Delay between compressor switch-off and start-up
(same compressor)
1 to 900 sec
120
L2
D06
2on
Delay between two different loads start-up
[0÷99.5] min, resolution 10 sec
10
N.V.
D07
2oF
Delay between two different loads switch-off
[0÷99.5] min, resolution 10 sec
10
N.V.
D08
don
Minimum time a stage stays switched on
[0÷99.5] min, resolution 10 sec
0
L2
D09
doF
Maximum time a stage stays switched on
[0.00÷24.00] hours, resolution 10 min
0:00
L2
D10
dnF
don delay enabled also for the first request
No (0-NO) - Yes (1-YES)
NO
L2
D11
MAo
doF delay enable also for the first switching off
No (0-NO) - Yes (1-YES)
NO
L2
D12
dn1
Low suction pressure alarm delay
0 to 999 sec
0
L2
D13
dF1
Low suction pressure error signal enabling
No (0-NO) - Yes (1-YES)
YES
L2
D14
LPd
Compressor minimum off time for high-pressure
switch protection
0 to 15 min
5
L2
D15
LPE
Number of high-pressure switch activations before
compressor lock
0 to 15
7
L2
D16
HPF
Bump start enable
No (0-NO) - Yes (1-YES)
NO
N.V.
D17
HPn
Bump start ambient threshold
-40°C to 110°C
0
N.V.
D18
bMP
Compressor stop time for next bump start
0 to 23 hours and 50 minutes
1:00
N.V.
D19
bMA
Compressor on time during bump function
1 to 15 sec
2
N.V.
D20
bMi
Compressor off time during bump function
1 to 15 sec
15
N.V.
D21
bon
Number of cycles during bump start
1 to 15
3
N.V.
D22
boF
DLT alarm temperature to stop compressor
-40°C to 180°C
140
L2
D23
bMn
DLT alarm recover temperature to turn on
compressor
-40°C to 180°C
90
L2
D24
dLt
DLT alarm activation delay
0 to 255 sec
30
L2
D25
dLr
Compressor minimum off time for DLT Alarm
0 to 255 min
5
L2
D26
dLd
Number of DLT alarm activations before compressor
lock
0 to 15
10
L2
D27
dCt
Time to ignore low DLT sensor error at start-up
0 to 255 min
5
L2
D28
dLn
Compressor minimum off time for low-pressure
switch protection
0 to 15 min
3
L2
D29
dLi
Low-pressure alarm value
0 to 15 bar
0.5
L1