Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
A14
P4F
Probe P4 calibration
-12°C to 12°C
0
L2
A15
P5C
Probe P5 configuration
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
Not used
L2
A16
P5F
Probe P5 calibration
-12°C to 12°C
0
L2
A17
P6C
Probe P6 configuration
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
Ambient temp
(NTC10K)
L2
A18
P6F
Probe P6 calibration
-12°C to 12°C
0.0
L2
A19
P7C
Probe P7 configuration
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
Not used
L2
A20
P7F
Probe P7 calibration
-12°C to 12°C
0
L2
A21
dPE
Delay before activating probe error
0 to 255 sec
0
L2
B01
Unt
Measurement unit for pressure
Bar (0-BAR)
– PSI (1-PSI) – KPA (2-TPA)
bar
L2
B02
CF
Measurement unit for temperature
°C (0-C)
°C
L2