C6.1.10/0118-0318/E
49
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
G38
Sd3
Holiday defrost start 5
0 to 23h50 minutes; nu
16:00
L2
G39
Sd4
Holiday defrost start 6
0 to 23h50 minutes; nu
20:00
L2
G40
Sd5
First weekly holiday
SUN (0-SUN)
MON (1-MON)
TUE (2-TUE)
WED (3-WED)
THU (4-THU)
FRI (5-FRI)
SAT (6-SAT)
nu (7-NU)
SUN
L2
G41
Sd6
Second weekly holiday
SUN
L2
G42
Hd1
Fans operating mode
cn = Parallel to compressor, off during defrost;
on = Fans always on, only off during defrost;
cy = Parallel to compressor, on during defrost;
oy = Fans permanently in operation
cn (0-CN)
on (1-ON)
cy (2-CY)
oy (3-OY);
cn
L2
G43
Hd2
Fans stop temperature
-40°C to 110°C
0
L2
G44
FnC
Temperature differential avoiding short cycles of fans 0 to 59°C
2
L2
G45
FSt
Fan On time
0 to 255 min
1
L2
G46
Fct
Fan Off time
0 to 255 min
1
L2
G47
Fon
Room probe selection for evaporator fan
management
NU (0-NU)
Mid-coil temperature (1-MCT)
Discharge line temperature (2-DLT)
Ambient temperature (3-AMT)
Thermostat temperature (4-TMT)
Not used
L2
G48
FoF
Maximum case temperature alarm threshold
G49 to 110°C
10
L2
G49
FAP
Minimum case temperature alarm threshold
-40°C to G48
-25
L2
G50
ALU
Case temperature alarm restart differential
0.1°C to 25.5°C
3
L2
G51
ALL
Case temperature alarm delay
0 to 255 sec
60
L2
G52
AHY
Exclusion of temperature alarm at start-up
0 to 255 min
20
L2
G53
ALd
Maximum door open time before alarm
0 to 255 min
3
L2
G54
dAO
Maximum length for light when door switch is closed
0 to 255 min
1
L2
G55
dSA
Fan delay after defrost
0 to 255 min
1
L2
H01
MdL
Current sensing 1
no; yes
YES
L2
H02
Fnd
Current sensing 2
no; yes
YES
L2