C6.1.10/0118-0318/E
42
Parameters
Description
Range
Factory setting
ZXDI
ZXDE
ZXDI
D30
LPF
Cold start enable
Disable (0) - Enable (1)
Disable
N.V.
D31
LPA
DLT temperature threshold to trip during cold start
-40 to 180°C
60
N.V.
D32
CSb
Suction pressure threshold to trip during cold start
-1.5 to 99.9 bar
0.5
N.V.
D33
CdL
Allowed number of cycles of DLT temperature trips
during cold start
1 to 15
4
N.V.
D34
CSL
Allowed number of cycles of low pressure trips during
cold start
1 to 15
4
N.V.
D35
Cdt
Compressor stop time during cold start
1 to 999 sec
180
N.V.
E01
CSt
Condenser fan motor modulation type
Not used (0-NU)
Fan cycling (1-CYC)
Modulated fan (2-MOD)
Modulated fan
L2
E02
CCs
Low setpoint for condenser fan map 1 (for R404A,
R507)
-40°C to HT1
10
N.V.
E03
FCM
Lower suction pressure point for condenser fan map
1 (for R404A, R507)
-1.5 bar to HP1; -21 PSI to HP1
3.3
N.V.
E04
LT1
High setpoint for condenser fan map 1 (for R404)
LT1 to 110°C
30
N.V.
E05
LP1
High suction pressure point for condenser fan map 1
(for R404A, R507)
LP1 to 99.9 bar; LP1 to 999 PSI
7.2
N.V.
E06
HT1
Low setpoint for condenser fan map 2 (for R134)
-40°C to HT2
25
N.V.
E07
HP1
Lower suction pressure point for condenser fan map
2 (for R404)
-1.5 bar to HP2; -21 PSI to HP2
2.5
N.V.
E08
LT2
High setpoint for condenser fan map 2 (for R134)
LT2 to 110°C
40
N.V.
E09
LP2
High suction pressure point for condenser fan map 2
(for R404)
LP2 to 99.9 bar; LP2 to 999 PSI
3.9
N.V.
E10
HT2
Low setpoint for condenser fan map 3 (for R22)
-40°C to HT3
20
N.V.
E11
HP2
Low suction pressure point for condenser fan map 3
(for R22)
-1.5 bar to HP3; -21PSI to HP3
5.2
N.V.
E12
LT3
High setpoint for condenser fan map 3 (for R22)
LT3 to 110°C
30
N.V.
E13
LP3
High suction pressure point for condenser fan map 3
(for R22)
LP3 to 99.9 bar; LP3 to 999 PSI
6.4
N.V.
E14
HT3
Low setpoint for condenser fan map 4 (for R407C)
-40°C to HT4
10
N.V.
E15
HP3
Lower suction pressure point for condenser fan map
4 (for R404)
-1.5 bar to HP4; -21 PSI to HP4
1.3
N.V.