64
Temperature and humidity parameters
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
Set the
hysteresis
independent of the type of threshold value specification.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Block
The switching output can be blocked using an object.
Threshold value setting using
Parameter •
Communication objects
Starting threshold value in 0.1% RH
valid until first communication
1 … 1000; 650
Object value limit (min.)
in 0.1%RH
1…1000
Object value limit (max.)
in 0.1%RH
1…1000
Type of threshold value change
Absolute value • Increase/decrease
Increment
(upon increase/decrease change)
0.1% RH • ... • 2.0% RH • ... • 20.0% RH
Hysteresis setting
in % • absolute
Hysteresis in 0.1% RH
0...1000; 100
Hysteresis in %
(relative to the threshold value)
0 … 50; 20
When the following conditions apply,
the output is
(TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects:
valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects:
valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(is only sent if periodically is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block
No • Yes
Содержание Salva KNX basic