36
Setting the parameters for all models
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
Then determine the value for the output object "smoke alarm: heat warning" in the
event of active heat warning and when it is to be sent.
Diagnostics memory
If the messages and warnings set above are to appear in the diagnostics memory, set
this function to "yes". Only the functions marked with "yes" are saved to the memory.
The latest error always has the number 1.
Messages are indicated with the date and time. For this, the time data must first be re-
ceived via the bus. Set whether the time and date are to be received as separate objects
or as one common object.
If time and date are received via two objects
, then a maximum of 10 seconds only may
elapse between receiving the date and receiving the time. Furthermore, a change of
date may not occur between receiving both objects. The objects must be received by
the device on the same day.
The diagnosis memory may be deleted with the input object 1512 "smoke alarm: diag-
nosis memory (1/0:delete)". Set the object value at which the memory is to be cleared.
For a diagnosis message, the output text is:
1513 "smoke alarm.: Diagnosis memory text: name": Equipment name.
1514 "smoke alarm.: diagnosis memory text: number": The latest message always has
the number 1.
1515 "smoke alarm: diagnosis memory text: type": Define a separate text for each type
of message
1516 "smoke alarm.: diagnosis memory text: date:".
1517 "smoke alarm.: diagnosis memory text: time:".
Set the texts for the individual messages that are output with it:
Object evaluation
1 = faulty • 0 = faulty
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Use diagnosis memory
No • Yes
Date and time will be set by
• two separate objects
• one common object
Clear diagnosis memory
• at value 1
• at value 0
• at value 0 or 1
Internal alarm active
[Free text max. 14 characters.]
Internal alarm inactive
[Free text max. 14 characters.]