51
Temperature and humidity parameters
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
8.3.
Temperature PI control
Activate the control if you want to use it.
General control
Set, in which cases
setpoint values and extension time
received via object are to
be retained. The parameter is only taken into consideration if the setting via object is
activated below. Please note that the setting "After power supply restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the 1st communication (setting via objects is ignored).
For an adequate regulation of the ambient temperature, comfort, standby, eco and
building protection modes may be used.
Comfort
when present,
Standby
during short absences,
Eco
as a night-time mode and
Frost/heat protection
(building protection) e. g. with the window open.
The settings for the temperature control include the setpoint temperatures for the in-
dividual modes. Objects are used to determine which mode is to be selected. A change
of mode may be triggered manually or automatically (e.g. by a timer, window contact).
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1
and periodically
if switching output = 1
send 1
Switching output sends on change to 0
and periodically
if switching output = 0
send 0
Use control
No • Yes
Maintain the
Target values and extension time received
via communication objects
• never
• after power supply restoration
• after power supply restoration and
programming